A dynamic nonlinear model for a once-through boiler-turbine unit in low load

被引:32
|
作者
Niu, Yuguang [1 ,3 ]
Du, Ming [1 ]
Ge, Weichun [2 ]
Luo, Huanhuan [2 ]
Zhou, Guiping [2 ]
机构
[1] North China Elect Power Univ, Sch Control & Comp Engn, Beijing 102206, Peoples R China
[2] State Grid Liaoning Elect Power Supply CO Ltd, Shenyang 110004, Liaoning, Peoples R China
[3] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
关键词
Nonlinear dynamic model; Once-through boiler; Low load; Nonlinear optimization algorithm; COORDINATED CONTROL; MATHEMATICAL-MODEL; CONTROLLER-DESIGN; CONTROL-SYSTEM; FUZZY MODEL; POWER-PLANT; VALIDATION; SIMULATION; ENERGY; EXERGY;
D O I
10.1016/j.applthermaleng.2019.113880
中图分类号
O414.1 [热力学];
学科分类号
摘要
Under the background of serious wind and solar energy curtailment in China, flexibility modification of coal-fired supercritical units is selected as an effective technical path to provide space for renewable energy into the grid. Modeling of coordinated control system in low load has yet to be conducted to date. In this work, a simplified dynamic model for coal-fired once-through boiler-turbine unit aimed at low load working condition is built up. First, the major model structure is established mainly based on mass and energy balance laws as well as thermodynamic equilibrium of important parameters combined with the analysis of operation characteristics. Then, the unknown parameters in the model are estimated by regression analysis, statistical analysis, and nonlinear optimization algorithm. Comparison results between measurement and simulation results show that the model has acceptable accuracy and, importantly, also captures the essential dynamic characteristics of units.
引用
收藏
页数:13
相关论文
共 50 条
  • [31] EXPERIMENTAL DYNAMIC CHARACTERISTICS OF A SUPERCRITICAL ONCE-THROUGH BOILER
    SULLER, PL
    ROMANOV, AF
    THERMAL ENGINEERING, 1973, 19 (05) : 79 - 86
  • [32] Coordinated Control of Once-through Boiler-turbine Units Using Feedforward-feedback Approach based on Stable Inversion
    Li, Lu
    Zeng, Deliang
    Chang, Taihua
    Lv, You
    2014 4TH AUSTRALIAN CONTROL CONFERENCE (AUCC), 2014, : 49 - 54
  • [33] Modernizing the heat load control system of a once-through boiler unit at a thermal power station using a dynamic corrector
    Yu. M. Kovrigo
    M. A. Konovalov
    A. S. Bunke
    Thermal Engineering, 2012, 59 (10) : 772 - 778
  • [34] ONCE-THROUGH BOILER CONTROL
    KENNY, PL
    POWER ENGINEERING, 1968, 72 (01) : 36 - &
  • [35] ONCE-THROUGH BOILER CONTROL
    KENNY, PL
    POWER ENGINEERING, 1968, 72 (02) : 58 - &
  • [36] CONTROLS FOR A ONCE-THROUGH BOILER
    LOUIS, JR
    INSTRUMENTS & CONTROL SYSTEMS, 1971, 44 (01): : 77 - &
  • [37] Improvement of an Elman Neural Network Model for Once-through Boiler Unit and Its Verification
    Xi, Yanna
    Wang, Yinsong
    Li, Ke
    PROCEEDINGS OF THE 28TH CHINESE CONTROL AND DECISION CONFERENCE (2016 CCDC), 2016, : 1867 - 1872
  • [38] Nonlinear dynamics and control of bifurcation to regulate the performance of a boiler-turbine unit
    Moradi, Hamed
    Alasty, Aria
    Vossoughi, Gholamreza
    ENERGY CONVERSION AND MANAGEMENT, 2013, 68 : 105 - 113
  • [39] A dynamic nonlinear model used for controller design of a 600 MW supercritical circulating fluidized bed boiler-turbine unit
    Zhang, Hongfu
    Gao, Mingming
    Yu, Haoyang
    Fan, Haohao
    Zhang, Jiahui
    APPLIED THERMAL ENGINEERING, 2022, 212
  • [40] EXTENDED LINEAR MATHEMATICAL MODEL FOR A POWER STATION UNIT WITH A ONCE-THROUGH BOILER.
    Borsi, Ladislaus
    1600, (03):