Flashover performance of ERV station post insulators covered with ice

被引:0
|
作者
Farzaneh, M [1 ]
Farzaneh-Dehkordi, J [1 ]
Zhang, J [1 ]
机构
[1] Univ Quebec Chicoutimi, NSERC Hydro Quebec, Ind Chair Atmospher Icing Power Network Equipment, Chicoutimi, PQ G1V 2M3, Canada
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The icing performance of standard- shed-design porcelain insulators, with a dry arcing distance of up to 4.17 in, corresponding to full-scale Hydro-Quebec 735 kV substation insulators, was investigated. Artificial ice was formed at -12degreesC in a climate room from supercooled water droplets produced by a set of pneumatic nozzles. The relationship between the maximum withstand voltage, Vws, and insulator length was determined. With an applied water conductivity of 30 muS/cm and an ice thickness of 15 mm, measured on a rotating monitoring cylinder, flashover may occur at service voltage. Moreover, the Vws of the ice-covered insulators tested increases non-linearly with an increase in insulator length. These results are of great importance for the design of EHV substation insulators used in cold climate regions.
引用
收藏
页码:37 / 40
页数:4
相关论文
共 50 条
  • [1] AC flashover performance of glass insulators covered with ice or snow at natural station
    Xiang, Ze
    Jiang, Xingliang
    Zhang, Zhijin
    Hu, Jianlin
    Jin, Xi
    Guo, Yujun
    Xiang, Z. (xiangze1987@163.com), 1600, Science Press (40): : 1345 - 1350
  • [2] Flashover performance of ice-covered insulators
    Farzaneh, M
    Kiernicki, J
    CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 1997, 22 (03): : 95 - 109
  • [3] AC flashover performance of insulators covered with artificial ice
    Universite du Quebec a Chicoutimi, Chicoutimi, Canada
    IEEE Trans Power Delivery, 2 (1038-1045):
  • [4] AC FLASHOVER PERFORMANCE OF INSULATORS COVERED WITH ARTIFICIAL ICE
    FARZANEH, M
    DRAPEAU, JF
    IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (02) : 1038 - 1051
  • [5] Flashover Performance of URV&ERV Post Insulators under Icing Conditions
    Xu, Zuoming
    Xu, Tao
    Tao, Yao
    Li Xuelin
    Jin, Li
    Chen Jiaxing
    Lin, Cai
    Ru, Jia
    2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 295 - 298
  • [6] FLASHOVER TESTS OF INSULATORS COVERED WITH ICE OR SNOW
    WATANABE, Y
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (05): : 1788 - 1794
  • [7] Flashover performance of 500 kV ice-covered porcelain post insulators with composite assistant shed
    Xu, Tao
    Wang, Hai-Ming
    Wang, Lin-Lin
    Xu, Zuo-Ming
    Yao, Tao
    Cai, Lin
    Gaodianya Jishu/High Voltage Engineering, 2012, 38 (01): : 167 - 172
  • [8] Study of DC Flashover Performance of Ice-covered Insulators at High Altitude
    Jiang, Xingliang
    Zhao, Shihua
    Hu, Jianlin
    Zhang, Zhijin
    Shu, Lichun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (02) : 391 - 400
  • [9] Flashover of ice- and snow-covered insulators
    Farzaneh, Masoud
    Chisholm, William A.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2007, 14 (06) : 1333 - 1333
  • [10] FLASHOVER TESTS OF INSULATORS COVERED WITH ICE OR SNOW.
    Watanabe, Y.
    1977,