Partial discharge detection and localization in power transformers

被引:0
|
作者
Gockenbach, E [1 ]
机构
[1] Univ Hannover, Inst Elect Power Syst, Div High Voltage Engn, Schering Inst, D-30167 Hannover, Germany
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An enhanced partial discharge (PD) measurement and evaluation techniques used for an improved condition assessment on power transformers are introduced and discussed. The PD measurement system itself is based on a wide-band electrical decoupling of the PD signals using special sensors, a superior signal transmission technology and the transfer function, thus the PD can be detected, localized and furthermore the influences of disturbing noise be significantly reduced during the online measurement. Remaining noises and pulses from outside the transformer are afterwards suppressed using improved digital signal processing tools. The measurements in the laboratory and on-site show reasonable results and the PD measuring system will be integrated as a component in a comprehensive monitoring and diagnostic system.
引用
收藏
页码:466 / 469
页数:4
相关论文
共 50 条
  • [21] Multichannel Detection of Acoustic Emissions and Localization of the Source with External and Internal Sensors for Partial Discharge Monitoring of Power Transformers
    Bua-Nunez, Iago
    Posada-Roman, Julio E.
    Garcia-Souto, Jose A.
    [J]. ENERGIES, 2021, 14 (23)
  • [22] Enhancing the Accuracy of Partial Discharge Localization in Power Transformers Using the UHF Measurement Technique
    Azirani, Mohammad Akbari
    Ariannik, Mohamadreza
    Werle, Peter
    Akbari, Asghar
    [J]. 2019 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2019, : 58 - 62
  • [23] Transfer function-based partial discharge localization in power transformers: A feasibility study
    Akbari, A
    Werle, P
    Borsi, H
    Gockenbach, E
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (05) : 22 - 32
  • [24] Quantitative Comparison of Partial Discharge Localization Algorithms on Power Transformers Based on Acoustic Method
    Wang, Yan-Bo
    Qin, Shao-Rui
    Wang, Liu-Fang
    Ding, Guo-Cheng
    Li, Jian-Lin
    Zhu, Tai-Yun
    Zhang, Guan-Jun
    [J]. 2018 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2018, : 542 - 545
  • [25] Investigating Suitable Positions in Power Transformers for Installing UHF Antennas for Partial Discharge Localization
    Mirzaei, H. R.
    Akbari, A.
    Zanjani, M.
    Miralikhani, K.
    Gockenbach, E.
    Borsi, H.
    [J]. PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 625 - 628
  • [26] Feasibility of Partial Discharge Localization in Power Transformers based on a novel Curve Fitting Method
    Rahimbakhsh, M.
    Mostoofi, M.
    Werle, P.
    Gockenbach, E.
    [J]. 2018 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2018, : 531 - 534
  • [27] Acoustic partial discharge localization methodology in power transformers employing the quantum genetic algorithm
    Liu, Hua-Long
    [J]. APPLIED ACOUSTICS, 2016, 102 : 71 - 78
  • [28] Partial discharge localization on dry-type transformers
    Szczechowski, Janusz
    Siodla, Krzysztof
    [J]. 2014 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2014,
  • [29] Partial Discharge Localization in Transformers Using UHF Sensors
    Sinaga, H. H.
    Phung, B. T.
    Ao, P. L.
    Blackburn, T. R.
    [J]. 2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 64 - 68
  • [30] Partial discharge diagnosis on large power transformers
    Gross, DW
    Söller, M
    [J]. CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 186 - 191