Partial Discharge Localization in Transformers Using UHF Sensors

被引:0
|
作者
Sinaga, H. H. [1 ]
Phung, B. T. [1 ]
Ao, P. L. [1 ]
Blackburn, T. R. [1 ]
机构
[1] Univ New S Wales, Sch Elect Engn & Telecommun, Sydney, NSW 2052, Australia
关键词
Partial discharge location; Ultra High Frequency (UHF); cumulative energy;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The location of the partial discharge (PD) source inside a transformer can be determined by using the time differences between signals that are captured by an array of three UHF sensors. However, other unwanted signals are also picked up by the sensors and may result in a false PD location. This paper discusses the application of multivariate denoising to the PD signals. Three methods are compared to determine the time difference between the received signals and locate the PD source. With the first peak method, the time difference is calculated by taking the first peak of the signal as the arrival instant. In the second method, the arrival time is determined from the knee point of the cumulative energy curve. For the third method, the time difference is determined by applying the similarity function to the plot of the cumulative energy of the PD signals. The last method is fully automated. However, experimental results show the first peak method tends to be the most accurate.
引用
收藏
页码:64 / 68
页数:5
相关论文
共 50 条
  • [1] Partial Discharge Localization in Transformers Using Monopole and Log-Spiral UHF Sensors
    Sinaga, H. H.
    Phung, B. T.
    Blackburn, T. R.
    [J]. 2012 IEEE 10TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM), 2012,
  • [2] Localization of partial discharges using UHF sensors in power transformers
    Shen, Z. B.
    El-Saadany, E. F.
    [J]. 2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 2660 - +
  • [3] Partial Discharge Localization in Transformers Using UHF Detection Method
    Sinaga, H. H.
    Phung, B. T.
    Blackburn, T. R.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (06) : 1891 - 1900
  • [4] Partial Discharge Source Localization using UHF Sensors
    Gohil, Nidhi J.
    Kundu, Prasanta
    Chowdhury, Anandita
    [J]. 2017 3RD INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2017, : 208 - 211
  • [5] Design and testing of UHF sensors for Partial Discharge detection in transformers
    Lopez-Roldan, J.
    Tang, T.
    Gaskin, M.
    [J]. PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1052 - +
  • [6] Partial discharge monitoring for power transformers using UHF sensors Part 1: Sensors and signal interpretation
    Judd, MD
    Yang, L
    Hunter, IBB
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2005, 21 (02) : 5 - 14
  • [7] Enhancing the Accuracy of Partial Discharge Localization in Power Transformers Using the UHF Measurement Technique
    Azirani, Mohammad Akbari
    Ariannik, Mohamadreza
    Werle, Peter
    Akbari, Asghar
    [J]. 2019 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2019, : 58 - 62
  • [8] On the UHF partial discharge measurement in transformers
    Kuppuswamy, R
    [J]. 2003 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2003, : 349 - 352
  • [9] Partial discharge monitoring for power transformers using UHF sensors - part 2: Field experience
    Judd, MD
    Yang, L
    Hunter, IBB
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2005, 21 (03) : 5 - 13
  • [10] Localization of Partial Discharge source in High Voltage apparatus using multiple UHF sensors
    Mishra, D. K.
    Sarkar, B.
    Koley, C.
    Roy, N. K.
    [J]. 2015 INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ENVIRONMENT: TOWARDS SUSTAINABLE GROWTH (ICEPE), 2015,