Diagnostic methods in revealing internal moisture in polymer housed metal oxide surge arresters

被引:14
|
作者
Lahti, K [1 ]
Kannus, K [1 ]
Nousiainen, K [1 ]
机构
[1] Tampere Univ Technol, Inst Power Engn, FIN-33101 Tampere, Finland
关键词
arresters; degradation; insulation; leak detection; moisture; partial discharges; polymers;
D O I
10.1109/TPWRD.2002.803694
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Diagnostic measurements performed for surge arresters are normally studied by evaluating their suitability to detect aging and degradation of metal oxide material. The suitability of different methods for revealing internal moisture in arresters has not been studied much. This aspect is considered in the paper based on measurement results obtained during a 1.5-yr laboratory test series conducted for six different types of polymer-housed distribution class arresters. AC power losses, third-harmonic content of resistive leakage current, dc leakage current, and partial discharge measurement results over the test period are given and discussed. Details of the measurement procedures suitable for measuring polymeric arresters with internal moisture are also studied. AC power loss and dc leakage current measurements were found to be good methods, whereas the other two can only be used as additional methods when diagnosing internal moisture in polymer-housed arresters.
引用
收藏
页码:951 / 956
页数:6
相关论文
共 50 条
  • [21] Physical and chemical characterization of polymer housed surge arresters tested under accelerated weathering
    Saldivar Guerrero, Ruben
    Lopez-Gonzalez, Francisco
    Hernandez-Corona, Ramiro
    Paniagua-Garcia, Gilberto
    ISEIM 2008: PROCEEDINGS OF 2008 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING, 2008, : 91 - 91
  • [22] An investigation of aging characteristics of polymer housed distribution surge arresters by accelerated aging test
    Kim, Juyong
    Park, Chulbae
    Jung, Yeunha
    Song, Ilkeun
    2008 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2008, : 593 - 596
  • [23] Electrothermal model for complete metal-oxide surge a arresters
    da Costa, EG
    Naidu, SR
    de Lima, AG
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2001, 148 (01) : 29 - 33
  • [24] A new Algorithm for the Design of Metal Oxide Varistor Surge Arresters
    Tarfulea, Nicolae
    Frigura-Iliasa, Flaviu Mihai
    Vatau, Doru
    Andea, Petru
    Balcu, Florin
    Macarie, Amalia Corina
    2016 IEEE 16TH INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING (EEEIC), 2016,
  • [25] Bibliography of metal oxide surge arresters, 1990-1992
    IEEE Trans Power Delivery, 3 (1285-1300):
  • [26] Metal-oxide resistor - at the heart of modern surge arresters
    Greuter, Felix
    Perkins, Roger
    Rossinelli, Marco
    Schmueckle, Friedrich
    ABB Review, 1989, (01): : 35 - 42
  • [27] Research on Live Detection Technology of Metal Oxide Surge Arresters
    Zhang, Yi
    Song, Hui
    Gao, Qiang
    Zhong, Dan-tian
    Sheng, Ge-hao
    Jiang, Xiu-chen
    2016 INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING AND AUTOMATION (ICEEA 2016), 2016,
  • [29] SURGE ARRESTERS - CONVENTIONAL TECHNOLOGY - METAL-OXIDE RESISTORS
    BURGER, U
    KNECHT, B
    BROWN BOVERI REVIEW, 1979, 66 (11): : 734 - 738
  • [30] THERMAL-PROPERTIES OF METAL-OXIDE SURGE ARRESTERS
    LAT, MV
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (07): : 2194 - 2202