摘要
Transformers are one of the most strategic components in balancing the voltage levels and hence a high priority is given to their performance [1]. It is established that, insulation technology plays a critical role in judging the performance and service life in oil filled apparatus [2]. Performance of the insulation system depends mainly on the deterioration behavior of insulation oil and paper. The mechanisms that are responsible for premature aging of oil/paper insulation are almost the same in all the oil filled apparatus. Yet, there will be a significant difference in the intensity of the aging mechanisms in different apparatus. This intensity is attributable to rating, design, and duration of operation for different machines. The detailed discussions on these mechanisms are presented in the subsequent sections of this paper. However, aging of service insulants is unavoidable and is to be maintained at a lower rate or arrested to the greatest possible extent, such that, catastrophic failures and unscheduled outages may be mitigated [3]. Normally, utilities follow scheduled condition monitoring activities to avoid the consequences of premature aging. Hence, knowledge on these in-service condition monitoring activities will be helpful in understanding the exact deterioration rate of the insulation system. Real time in-service experience of several transformer fleets that belong to United Kingdom utilities are reported in [4]. An early degradation of insulation is noticed through increase in acidity and furan concentration in oil for several transformers in the fleet. Authors investigated this early degradation in different perspectives including loading conditions, manufacturers, and oil chemistry changes. It is inferred that changes in oil chemistry is an important attribute for early degradation and hence utilities are advised to adopt different asset management strategies for affected and unaffected transformers in a fleet. Recently, failure rate data of service aged transformer fleets of an Australian utility were analyzed to establish the relationship between aging and different failure types [5]. It is noticed that degradation of the insulation system will be rapid after 20 years of service aging thus entailing the frequent condition monitoring activities after 20 years to identify premature aging failures.
引用
收藏
页码:33 / 42
页数:10
相关论文
共 50 条
  • [1] Condition Monitoring of Oil-filled Transformers using Unsupervised Classification Techniques
    Eke, Samuel
    Aka-Ngnui, Thomas
    Clerc, Guy
    Fofana, Issouf
    2017 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENON (CEIDP), 2017, : 189 - 192
  • [2] A Relevant Condition Monitoring of Corrosive Sulphur Deposition on the Windings of Oil-Filled Electrical Transformers
    Jadim, R.
    Kans, M.
    Rehman, S.
    Alhems, L. M.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (05) : 1736 - 1742
  • [3] Improving accuracy of DGA interpreation of oil-filled power transformers needed for effective condition monitoring
    Suleiman, Abubakar A.
    Alghamdi, Ali S.
    Mohamad, Nor Asiah
    Bashir, Nouruddeen
    Aizam, Mohd
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 374 - 378
  • [4] Condition assessment of Oil-filled Rectifier Transformers in a Smelter Plant by On-line Acoustic Emission Technique - Case studies
    Shanker, T. Bhavani
    Shyam, R.
    Vaidhyanathan, V.
    Mohamed, A. Sheik
    2022 IEEE 6TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS, CATCON, 2022, : 446 - 450
  • [5] Physical-chemical oil tests, monitoring and diagnostics of oil-filled transformers
    Gradnik, MK
    PROCEEDINGS OF THE 2002 IEEE 14TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2002, : 242 - 247
  • [6] A Novel Condition Monitoring Procedure for Early Detection of Copper Corrosion Problems in Oil-Filled Electrical Transformers
    Jadim, Ramsey
    Kans, Mirka
    Alhattab, Mohammed
    Alhendi, May
    ENERGIES, 2021, 14 (14)
  • [7] METHOD FOR SEALING OIL-FILLED TRANSFORMERS THAT INCREASES THE SERVICE LIFE OF THE SEALS.
    Markovich, L.M.
    Smorygo, L.N.
    Kuz'min, G.A.
    Kopylov, A.I.
    Babak, T.Z.
    Popov, A.V.
    Soviet electrical engineering, 1987, 58 (01): : 111 - 112
  • [8] Programmable electronic instrument for condition monitoring of in-service power transformers
    Poza, F
    Mariño, P
    Otero, S
    Machado, F
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2006, 55 (02) : 625 - 634
  • [9] On-line diagnostics of oil-filled transformers
    Varl, A
    PROCEEDINGS OF THE 2002 IEEE 14TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2002, : 253 - 257
  • [10] Rapid Assessment of the Operational Status of the Oil-filled Transformers
    Levin, Vladimir
    Kerimkulov, Nurzhan
    2016 11TH INTERNATIONAL FORUM ON STRATEGIC TECHNOLOGY (IFOST), PTS 1 AND 2, 2016,