Fault Location in Neutral Non-effectively Grounded Distribution Systems Using Phase Current and Line-to-line Voltage

被引:8
|
作者
Tang, Jinrui [1 ]
Yin, Xianggen [1 ]
Wen, Minghao [1 ]
Zhang, Zhe [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
distribution systems; fault location; non-effectively grounding; traveling wave; NETWORKS; SIGNALS;
D O I
10.1080/15325008.2014.933367
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A scheme of single-line-to-ground fault location in neutral non-effectively grounded distribution systems is proposed in this article. The characteristics of phase current traveling waves and line-to-line voltage traveling waves are analyzed. The wavelet transform technique is used to extract the information of the arrival times, polarities, and amplitudes of the recorded traveling waves. The fault location scheme can simultaneously realize faulty feeder identification, fault section location, and fault position location even if only two-phase current transformers are installed in the Phases A and C and feeder terminal units only to provide line-to-line voltage information. The effectiveness and practicability of the proposed scheme have been verified by PSCAD/EMTDC simulation results.
引用
收藏
页码:1371 / 1385
页数:15
相关论文
共 50 条
  • [31] Novel adaptive protection principle of the single-phase earth fault of the non-effectively grounded power systems
    Electrical Engineering Department, Huazhong University of Science and Technology, Wuhan 430074, China
    Zhongguo Dianji Gongcheng Xuebao, 2006, 2 (52-57):
  • [32] Traveling-Wave Based Fault Location for Phase-to-Ground Fault in Non-Effectively Earthed Distribution Networks
    Wang, Yani
    Zheng, Tao
    Yang, Chang
    Yu, Li
    ENERGIES, 2020, 13 (19)
  • [33] Faulty feeder detection based on image recognition of voltage-current waveforms in non-effectively grounded distribution networks
    Yuan, Jiawei
    Wu, Tong
    Hu, Yanjie
    Jiao, Zaibin
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 143
  • [34] Study on line selection in non-effectively grounded system based on wavelet transform and Wiener filter
    Qi, Z
    Yang, YH
    2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, 2004, : 89 - 93
  • [35] Research on eigenparameters and detection methods for single-phase-to-ground faults in non-effectively grounded distribution systems
    Sheng, Wanxing
    Song, Xiaohui
    IET CYBER-PHYSICAL SYSTEMS: THEORY & APPLICATIONS, 2023, 8 (03) : 205 - 217
  • [36] Study on the Mechanism and Electrical Characterization of the Distribution Porcelain Insulator Incipient Fault in the Non-Effectively Grounded System
    Cong, Zihan
    Liu, Yadong
    Yan, Yingjie
    Wang, Ke
    Jiang, Xiuchen
    IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (03) : 1840 - 1851
  • [37] Location method of high-impedance fault based on transient zero-sequence factor in non-effectively grounded distribution network
    Li, Lin
    Gao, Houlei
    Yuan, Tong
    Peng, Fang
    Xue, Yongduan
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 226
  • [38] Suppressing circulating current in the modular multilevel converter using line-to-line voltage correction modules
    Harave, Sudarshan Tejanag
    Mancilla-David, Fernando
    2019 51ST NORTH AMERICAN POWER SYMPOSIUM (NAPS), 2019,
  • [39] A New Method for Faulted Line Identification in Neutral Non-grounded Distribution Systems
    Li Dan
    Wang Fangzong
    MANUFACTURING SCIENCE AND TECHNOLOGY, PTS 1-8, 2012, 383-390 : 2496 - 2500
  • [40] Characteristic Analysis and Fault Segment Location on Negative Sequence Voltage and Current of Single Phase Line Breakage Fault in Distribution Network
    Chang Z.
    Song G.
    Zhang W.
    Dianwang Jishu/Power System Technology, 2020, 44 (08): : 3065 - 3072