A new way of two-terminal fault location for transmission lines based on strong tracking filter

被引:0
|
作者
Liu Meng [1 ]
Liu Suling [1 ]
机构
[1] Hebei Univ, Coll Phys Sci & Technol, Baoding, Peoples R China
关键词
strong tracking filter; sequence component; parameter estimation; two-terminal ranging method;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
When the high-voltage transmission lines break down, the fault point should be separated from the network. In order to locate the fault point quickly and accurately, a new fault location method of two-terminal based on sequence components and strong tracking filter theory is presented. This paper proposes a method that using the fault distance as the state variable and failure voltage and failure current measured at two terminals as input variables, the system state and parameter joint estimation model is built. Using method of strong tracking filter to estimate fault distance, fault location can be found within a short time after accident. Using sequence component equation can unify form of state equation regardless of the type of fault. MATLAB program with a large number of fault data shows that the method with short time of location and accurate results is a very effective way to fault location.
引用
收藏
页码:1047 / 1051
页数:5
相关论文
共 50 条
  • [41] An iterative two-terminal fault-location method based on unsynchronized phasors
    Dalcastagne, Andre Luis
    Noceti Filho, Sidnei
    Zuern, Hans Helmut
    Seara, Rui
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 2318 - 2329
  • [42] The system research of two-terminal fault location analysis based on recording wave
    Yang, Yongfeng
    Sun, Yue
    Ren, Ju
    2010 INTERNATIONAL CONFERENCE ON MANAGEMENT SCIENCE AND ENGINEERING (MSE 2010), VOL 5, 2010, : 193 - 197
  • [43] Two Terminal Instantaneous Power-Based Fault Classification and Location Techniques for Transmission Lines
    Muzzammel, Raheel
    Arshad, Rabia
    Raza, Ali
    Sobahi, Nebras
    Alqasemi, Umar
    SUSTAINABILITY, 2023, 15 (01)
  • [44] Single-Ended Traveling Wave Based Fault Location on Two Terminal Transmission Lines
    Eng, Ngu Eng
    Ramar, Krishnathevar
    TENCON 2009 - 2009 IEEE REGION 10 CONFERENCE, VOLS 1-4, 2009, : 2192 - 2195
  • [45] Gaussian Process Regression-Based Predictive Fault Location Algorithm for Three-Terminal Lines Using Two-Terminal PMUs
    Badran, Osama
    Rizk, Mohammad E. M.
    Hu, Weihao
    Abulanwar, Sayed
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2024, 39 (04) : 5829 - 5853
  • [46] Accuracy analysis using the EMD and VMD for two-terminal transmission line fault location based on traveling wave theory
    Oliveira, A. P.
    Moreira, F. A.
    Picanco, A. F.
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 224
  • [47] A two-terminal fault location algorithm using asynchronous data based on phase characteristics for high voltage transmission line
    Chen, Xu
    Zhu, Yongli
    Guo, Xiaohong
    Gao, Yanfeng
    Zhao, Lei
    Zhao, Xuesong
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (22): : 152 - 156
  • [48] Fault location method on two-terminal transmission line using synchronized time information of traveling waves
    Akmaz, Duzgun
    Mamis, Mehmet Salih
    ELECTRICAL ENGINEERING, 2022, 104 (02) : 979 - 990
  • [49] Fault location method on two-terminal transmission line using synchronized time information of traveling waves
    Düzgün Akmaz
    Mehmet Salih Mamiş
    Electrical Engineering, 2022, 104 : 979 - 990
  • [50] Unsynchronised two-terminal transmission-line fault-location without using line parameters
    Liao, Y.
    Elangovan, S.
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2006, 153 (06) : 639 - 643