Modelling and experimental investigation of the cross-flow dew point evaporative cooler with and without dehumidification

被引:67
|
作者
Lin, J. [1 ]
Wang, R. Z. [2 ]
Kumja, M. [1 ]
Bui, T. D. [1 ]
Chua, K. J. [1 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, 9 Engn Dr 1, Singapore 117575, Singapore
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
基金
新加坡国家研究基金会;
关键词
Cross-flow; Dew point evaporative cooling; Performance; Experiment; Modeling; CYCLE HEAT-EXCHANGERS; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2017.04.047
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper investigates the cooling potential of a cross-flow dew point evaporative cooler under various conditions. Preliminary study reveals that the dew point evaporative cooler's performance does not approach its designed capacity when the ambient humidity goes beyond the thermal comfort zone. To address this problem, an air dehumidification process is proposed before the evaporative cooling takes place. It is observed that the cross-flow cooler is able to achieve improved cooling effectiveness when an appropriate inlet air humidity condition is realized. The influence of different dehumidification levels on its cooling capacity and efficiency is subsequently analyzed. Additionally, a mathematical model is developed to predict the cooler performance. Key findings from this study are: (1) The maximum discrepancy between the simulation results and experimental data is within +/- 3.0%; (2) the overall wet bulb and dew point effectiveness of the cross-flow cooler can reach 1.25 and 0.85 for cooling of the supply air with moderate humidity; (3) the respective wet bulb effectiveness, cooling capacity and COP of the cross-flow system are 0.86, 2.2 kW and 4.6 under humid ambient air condition; and (4) the dehumidification of the supply air enables the cooling capacity and energy efficiency to be improved by 70-135%. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 13
页数:13
相关论文
共 50 条
  • [31] Performance measurement of a cross-flow indirect evaporative cooler: Effect of water nozzles and airflows arrangement
    De Antonellis, Stefano
    Joppolo, Cesare Maria
    Liberati, Paolo
    ENERGY AND BUILDINGS, 2019, 184 : 114 - 121
  • [32] Theoretical study on a cross-flow direct evaporative cooler using honeycomb paper as packing material
    Dai, YJ
    Sumathy, K
    APPLIED THERMAL ENGINEERING, 2002, 22 (13) : 1417 - 1430
  • [33] Numerical analysis of cross-flow plate type indirect evaporative cooler: Modeling and parametric analysis
    Adam, Abdalazeem
    Han, Dong
    He, Weifeng
    Chen, Junjie
    APPLIED THERMAL ENGINEERING, 2021, 185
  • [34] Performance prediction for modified design of dew point evaporative cooler for air cooling
    Patunkar, Prashant
    Dingare, Sunil
    AUSTRALIAN JOURNAL OF MECHANICAL ENGINEERING, 2024, 22 (04) : 666 - 677
  • [35] The counter-flow dew point evaporative cooler: Analyzing its transient and steady-state behavior
    Lin, Jie
    Duc Thuan Bui
    Wang, Ruzhu
    Chua, Kian Jon
    APPLIED THERMAL ENGINEERING, 2018, 143 : 34 - 47
  • [36] Energetic and exergetic performance investigation of a cross-flow regenerative indirect evaporative cooler made up of aluminium plate heat exchangers
    Inanli, Mert
    Aydin, Devrim
    Rezaei, Marzieh
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2023, 238 (06) : 2821 - 2833
  • [37] Performance evaluation of counter flow dew-point evaporative cooler with a three-dimensional numerical model
    Zhu, Guangya
    Chen, Weijian
    Zhang, Dalin
    Wen, Tao
    APPLIED THERMAL ENGINEERING, 2023, 219
  • [38] An improved indirect evaporative cooler experimental investigation
    Shahzad, Muhammad Wakil
    Burhan, Muhammad
    Ybyraiymkul, Doskhan
    Oh, Seung Jin
    Ng, Kim Choon
    APPLIED ENERGY, 2019, 256
  • [39] Experimental study on a cross-flow regenerative indirect evaporative cooling system
    Cui, Xin
    Tian, Wei
    Yang, Xiaohu
    Kong, Qiongxiang
    Chai, Yue
    Jin, Liwen
    CLEANER ENERGY FOR CLEANER CITIES, 2018, 152 : 395 - 400
  • [40] Manufacturing and experimental analysis of a dew-point indirect evaporative cooler using fused deposition modelling 3D printing and polymeric materials
    Castillo-Gonzalez, Jesus
    Comino, Francisco
    Navas-Martos, Francisco J.
    de Adana, Manuel Ruiz
    APPLIED THERMAL ENGINEERING, 2023, 230