Modelling and experimental investigation of the cross-flow dew point evaporative cooler with and without dehumidification

被引:67
|
作者
Lin, J. [1 ]
Wang, R. Z. [2 ]
Kumja, M. [1 ]
Bui, T. D. [1 ]
Chua, K. J. [1 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, 9 Engn Dr 1, Singapore 117575, Singapore
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
基金
新加坡国家研究基金会;
关键词
Cross-flow; Dew point evaporative cooling; Performance; Experiment; Modeling; CYCLE HEAT-EXCHANGERS; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2017.04.047
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper investigates the cooling potential of a cross-flow dew point evaporative cooler under various conditions. Preliminary study reveals that the dew point evaporative cooler's performance does not approach its designed capacity when the ambient humidity goes beyond the thermal comfort zone. To address this problem, an air dehumidification process is proposed before the evaporative cooling takes place. It is observed that the cross-flow cooler is able to achieve improved cooling effectiveness when an appropriate inlet air humidity condition is realized. The influence of different dehumidification levels on its cooling capacity and efficiency is subsequently analyzed. Additionally, a mathematical model is developed to predict the cooler performance. Key findings from this study are: (1) The maximum discrepancy between the simulation results and experimental data is within +/- 3.0%; (2) the overall wet bulb and dew point effectiveness of the cross-flow cooler can reach 1.25 and 0.85 for cooling of the supply air with moderate humidity; (3) the respective wet bulb effectiveness, cooling capacity and COP of the cross-flow system are 0.86, 2.2 kW and 4.6 under humid ambient air condition; and (4) the dehumidification of the supply air enables the cooling capacity and energy efficiency to be improved by 70-135%. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 13
页数:13
相关论文
共 50 条
  • [21] Theoretical Analysis of Geometrically Modified Dew Point Evaporative Cooler
    Patunkar, Prashant
    Dingare, Sunil V.
    PROCEEDINGS OF ASME 2021 INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION (IMECE2021), VOL 11, 2021,
  • [22] On the fundamental heat and mass transfer analysis of the counter-flow dew point evaporative cooler
    Lin, Jie
    Duc Thuan Bui
    Wang, Ruzhu
    Chua, Kian Jon
    APPLIED ENERGY, 2018, 217 : 126 - 142
  • [23] Towards a thermodynamically favorable dew point evaporative cooler via optimization
    Lin, Jie
    Wang, Ruzhu
    Li, Chuan
    Wang, Sibao
    Long, Jianyu
    Chua, Kian Jon
    ENERGY CONVERSION AND MANAGEMENT, 2020, 203
  • [24] Impact of air distribution on dew point evaporative cooler thermal performance
    Pacak, Anna
    Sierpowski, Korneliusz
    Malecha, Ziemowit
    Worek, William
    Cetin, Sabri
    Pandelidis, Demis
    APPLIED THERMAL ENGINEERING, 2023, 224
  • [25] Numerical study and optimization of the cross-flow Maisotsenko cycle indirect evaporative air cooler
    Pandelidis, Demis
    Anisimov, Sergey
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 103 : 1029 - 1041
  • [26] Numerical study on parametric correlations and regional applicability of a cross-flow indirect evaporative cooler
    Gao, Wenxue
    Yang, Mingchang
    Wang, Yan
    Yang, Lin
    Miao, Qingwei
    Yan, Rongsong
    Hu, Yingjie
    JOURNAL OF BUILDING ENGINEERING, 2024, 97
  • [27] Heat Exchanger Improvement of a Counter-Flow Dew Point Evaporative Cooler Through COMSOL Simulations
    Garcia-Gonzalez, Mario
    Cheng, Guanggui
    Bui, Duc Thuan
    Lopez-Leyva, Josue Aaron
    THERMO, 2024, 4 (04): : 475 - 489
  • [28] EXPERIMENTAL INVESTIGATION OF JETS IN A CROSS-FLOW
    ANDREOPOULOS, J
    RODI, W
    JOURNAL OF FLUID MECHANICS, 1984, 138 (JAN) : 93 - 127
  • [29] Experimental investigation into the thermal-flow performance characteristics of an evaporative cooler
    Heyns, J. A.
    Kroeger, D. G.
    APPLIED THERMAL ENGINEERING, 2010, 30 (05) : 492 - 498
  • [30] Integrated solar - Windcatcher with dew-point indirect evaporative cooler for classrooms
    Harrouz, Jean Paul
    Ghali, Kamel
    Ghaddar, Nesreen
    APPLIED THERMAL ENGINEERING, 2021, 188