Modelling and experimental investigation of the cross-flow dew point evaporative cooler with and without dehumidification

被引:67
|
作者
Lin, J. [1 ]
Wang, R. Z. [2 ]
Kumja, M. [1 ]
Bui, T. D. [1 ]
Chua, K. J. [1 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, 9 Engn Dr 1, Singapore 117575, Singapore
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
基金
新加坡国家研究基金会;
关键词
Cross-flow; Dew point evaporative cooling; Performance; Experiment; Modeling; CYCLE HEAT-EXCHANGERS; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2017.04.047
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper investigates the cooling potential of a cross-flow dew point evaporative cooler under various conditions. Preliminary study reveals that the dew point evaporative cooler's performance does not approach its designed capacity when the ambient humidity goes beyond the thermal comfort zone. To address this problem, an air dehumidification process is proposed before the evaporative cooling takes place. It is observed that the cross-flow cooler is able to achieve improved cooling effectiveness when an appropriate inlet air humidity condition is realized. The influence of different dehumidification levels on its cooling capacity and efficiency is subsequently analyzed. Additionally, a mathematical model is developed to predict the cooler performance. Key findings from this study are: (1) The maximum discrepancy between the simulation results and experimental data is within +/- 3.0%; (2) the overall wet bulb and dew point effectiveness of the cross-flow cooler can reach 1.25 and 0.85 for cooling of the supply air with moderate humidity; (3) the respective wet bulb effectiveness, cooling capacity and COP of the cross-flow system are 0.86, 2.2 kW and 4.6 under humid ambient air condition; and (4) the dehumidification of the supply air enables the cooling capacity and energy efficiency to be improved by 70-135%. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 13
页数:13
相关论文
共 50 条
  • [1] Visualized experimental investigation on cross-flow indirect evaporative cooler with condensation
    Meng, Dandong
    Lv, Jian
    Chen, Yi
    Li, Han
    Ma, Xuejian
    APPLIED THERMAL ENGINEERING, 2018, 145 : 165 - 173
  • [2] Investigation of dew point evaporative cooling with vacuum membrane dehumidification
    Lin, Jie
    Duc Thuan Bui
    Wang, Ruzhu
    Chua, Kian Jon
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 3851 - 3856
  • [3] Combining liquid desiccant dehumidification with a dew-point evaporative cooler: A design analysis
    Woods, Jason
    Kozubal, Eric
    HVAC&R RESEARCH, 2013, 19 (06): : 663 - 675
  • [4] Experimental and numerical investigation of a high-efficiency dew-point evaporative cooler
    Liu, Yuting
    Akhlaghi, Yousef Golizadeh
    Zhao, Xudong
    Li, Junming
    ENERGY AND BUILDINGS, 2019, 197 : 120 - 130
  • [5] Development of an experimental validated model of cross-flow indirect evaporative cooler with condensation
    Zheng, Bin
    Guo, Chunmei
    Chen, Tong
    Shi, Qi
    Lv, Jian
    You, Yuwen
    APPLIED ENERGY, 2019, 252
  • [6] Experimental and numerical investigation of novel dew-point evaporative cooler with shell and tube design
    Sulaiman, Mohammed A.
    Saber, Hindren Ali
    Hasan, Hasan F.
    Benim, Ali Cemal
    ENERGY, 2025, 317
  • [7] Numerical investigation of a novel tubular dew-point evaporative cooler
    Gao, Fangrui
    Thu, Kyaw
    Wang, Sibao
    Zhao, Fangyuan
    Lin, Jie
    Wu, Kaiyao
    APPLIED THERMAL ENGINEERING, 2023, 223
  • [8] The Theoretical and Experimental Researches on a Kind of Dew Point Indirect Evaporative Cooler
    Wang Baohong
    Liu Zhongbao
    Cui Jinju
    ADVANCES IN CHEMICAL ENGINEERING II, PTS 1-4, 2012, 550-553 : 2685 - +
  • [9] On-site experimental testing of a novel dew point evaporative cooler
    Bruno, Frank
    ENERGY AND BUILDINGS, 2011, 43 (12) : 3475 - 3483
  • [10] On the exergy analysis of the counter-flow dew point evaporative cooler
    Lin, Jie
    Bui, Duc Thuan
    Wang, Ruzhu
    Chua, Kian Jon
    ENERGY, 2018, 165 : 958 - 971