Fault detection of low global warming potential refrigerant supermarket refrigeration system: Experimental investigation

被引:18
|
作者
Sun, Jian [1 ]
Im, Piljae [2 ]
Bae, Yeonjin [2 ]
Munk, Jeff [2 ]
Kuruganti, Teja [3 ]
Fricke, Brain [1 ]
机构
[1] Oak Ridge Natl Lab, Bldg & Transportat Sci Div, One Bethel Valley Rd, Oak Ridge, TN 37830 USA
[2] Oak Ridge Natl Lab, Electrificat & Energy Infrastruct Div, One Bethel Valley Rd, Oak Ridge, TN 37830 USA
[3] Oak Ridge Natl Lab, Computat Sci & Engn Div, One Bethel Valley Rd, Oak Ridge, TN 37830 USA
关键词
Fault detection and diagnostics; Supermarket refrigeration; Experimental study; Global warming potential (GWP); BUILDING SYSTEMS; DIAGNOSIS; PROGNOSTICS;
D O I
10.1016/j.csite.2021.101200
中图分类号
O414.1 [热力学];
学科分类号
摘要
As one of the most energy-intensive end-uses in the commercial buildings sector, supermarkets consume around 50 kWh/ft(2) (or 537.6 kWh/m(2)) of electricity annually, or more than 2 million kWh of electricity per year for a typical store. The biggest consumer of energy in a supermarket is its refrigeration system, which accounts for 40-60% of its total electricity usage and is equivalent to about 2-3% of the total energy consumed by commercial buildings in United States, or around 0.5 quadrillion Btu (or 0.53 quadrillion KJ). Also, the supermarket refrigeration system is one of the biggest consumers of refrigerants. Current supermarket refrigeration systems rely on high global warming potential hydrofluorocarbon refrigerants. Reducing refrigerant usage or using environment friendly alternatives can result in significant climate benefits. The refrigeration system can also be adapted to handle flexible building loads and be integrated into grid response transactive control to balance the supply and demand of the electric grid. Even minor improvements in the efficiency and operational reliability of supermarket refrigeration systems can create significant value in terms of saving energy, improving food quality, protecting the environment, reducing carbon footprint, and enhancing electric grid resilience. Fault detection and diagnostics (FDD) techniques can be used to support refrigeration system operators in achieving these benefits. However, compare to FDD of other building heating, ventilation and air-conditioning and refrigeration (HVAC&R) equipment and systems which has attracted extensive FDD studies for decades, FDD of supermarket refrigeration systems, especially for low GWP refrigerant supermarket refrigeration system, has not gained enough attention from researchers. One of the key challenges is lack of available testing datasets to benchmark the system performance and record the faulted performance for system FDD research. This study selects several common faults of supermarket refrigeration systems, including display case door open, ice accumulation, expansive valve failure, and fan failure, to conduct experimental study to identify their fault characteristics, benchmark their faulted performance, then create a FDD characteristics matrix to support next step research on the development of supermarket refrigeration system FDD methods and field automated FDD implementation.
引用
收藏
页数:12
相关论文
共 50 条
  • [41] Experimental study on diffusion absorption refrigerator achieving 0.2 coefficient of performance using low global warming potential refrigerant and low-grade heat source
    Choi, Hyung Won
    Lee, Jae Won
    Kang, Yong Tae
    APPLIED THERMAL ENGINEERING, 2022, 201
  • [42] Investigation and Analysis of R463A as an Alternative Refrigerant to R404A with Lower Global Warming Potential
    Saengsikhiao, Piyanut
    Taweekun, Juntakan
    Maliwan, Kittinan
    Sae-ung, Somchai
    Theppaya, Thanansak
    ENERGIES, 2020, 13 (06)
  • [43] An experimental analysis of the effect of refrigerant charge level on an automotive refrigeration system
    Ratts, EB
    Brown, JS
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2000, 39 (05) : 592 - 604
  • [44] Theoretical evaluation of supermarket refrigeration systems using R1234ze(E) as an alternative to high-global warming potential refrigerants
    Gullo, Paride
    Cortella, Giovanni
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2016, 22 (08) : 1145 - 1155
  • [45] Dispersion Modeling of Leaks of Low Global Warming Potential Refrigerant HFO-1234yf in an Automobile Garage
    Koban, Mary E.
    Herrmann, David D.
    PROCESS SAFETY PROGRESS, 2011, 30 (01) : 27 - 34
  • [46] Fault detection for the refrigerant inventory of the system air conditioner
    Tae, Sang-Jin
    Cho, Keumnam
    Youn, Back
    Moon, Je-Myung
    Kim, Jong-Yup
    Kwon, Hyung-Jin
    PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 35 - +
  • [47] Investigation of the effect of superheating on the performance of a refrigeration system using low temperature different refrigerant blends in porous media
    Tarawneh, Mohammad
    Jawarneh, Ali M.
    Tlilan, Hitham
    Ababneh, Amer
    Al-Migdady, Ahmad
    HEAT TRANSFER-ASIAN RESEARCH, 2019, 48 (06): : 2216 - 2236
  • [48] Numerically Optimized Ejector Geometry for Ejector Refrigeration Systems With Low-Global Warming Potential Working Fluids
    Suresh, Ronanki
    Prakash, Ranjith
    Praveen, Visakh
    Datta, Santanu Prasad
    JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2024, 146 (10):
  • [49] An Experimental Investigation on Vapor Compression Refrigeration System Cascaded with Ejector Refrigeration System
    Kumar, Vikas
    Sachdeva, Gulshan
    Tiwari, Sandeep
    Anuradha, Parinam
    Jain, Vaibhav
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2021, 29 (03)
  • [50] Modelling the barriers to low global warming potential refrigerants adoption in developing countries: A case of Indian refrigeration industry
    Sanguri, Kamal
    Ganguly, Kunal
    Pandey, Aman
    JOURNAL OF CLEANER PRODUCTION, 2021, 280