Characterisation of vibration signals using continuous wavelet transform for condition assessment of on-load tap-changers

被引:19
|
作者
Kang, P
Birtwhistle, D
机构
[1] United Technol Res Ctr, E Hartford, CT 06108 USA
[2] Queensland Univ Technol, Brisbane, Qld Q4001, Australia
关键词
D O I
10.1006/mssp.2002.1525
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The operation of an on-load tap-changer (OLTC) on a high-voltage power transformer produces a vibration signal that consists of a series of well-defined transients. Due to the harmonic and non-stationary nature of transient. vibration signals, the traditional frequency and time-frequency techniques are not effective for characterising this type of vibration signal. The time domain features such as delays in time between transients, and the number and strengths of transients are more important for the assessment of the OLTC condition; This paper details the development of an OLTC vibration signal characterisation technique using the continuous wavelet transform (CWT). The CWT, due to its capability of multi-scale localisation in the time domain, is an effective tool in extracting the essential features from the original signals. These features are utilised to provide reliable indications of the health of the equipment. Signals from real plant are used to demonstrate the usefulness of the proposed technique. (C) 2003 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:561 / 577
页数:17
相关论文
共 50 条
  • [1] Condition assessment of power transformer on-load tap-changers using wavelet analysis
    Kang, PJ
    Birtwhistle, D
    IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (03) : 394 - 400
  • [2] Condition assessment of power transformer on-load tap-changers (OLTC) using wavelet analysis
    Kang, P
    Birtwhistle, B
    PICA 2001: 22ND IEEE POWER ENGINEERING SOCIETY INTERNATIONAL CONFERENCE ON POWER INDUSTRY COMPUTER APPLICATIONS, 2001, : 330 - 335
  • [3] BS FOR ON-LOAD TAP-CHANGERS
    WIGHTMAN, GG
    ELECTRICAL REVIEW, 1970, 186 (21): : 774 - &
  • [4] Condition Monitoring of On-Load Tap-Changers in Converter Transformers based on Vibration Method
    Duan, Ruochen
    Zuo, Yiwen
    Zheng, Hong
    Yao, Rong
    Deng, Menghua
    Sun, Zhiyi
    2018 2ND IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2018,
  • [5] A Collective Condition Monitoring Algorithm for On-Load Tap-Changers
    Feizifar, Behnam
    Mueller, Zdenek
    Fandi, Ghaeth
    Usta, Omer
    2019 IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2019 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2019,
  • [6] BRITISH STANDARD FOR ON-LOAD TAP-CHANGERS
    BIRD, MA
    ELECTRICAL REVIEW, 1970, 186 (17): : 606 - &
  • [7] On reverse control action of on-load tap-changers
    Yorino, N
    Funahashi, A
    Sasaki, H
    Galiana, FD
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1997, 19 (08) : 541 - 548
  • [8] COMMENTS ON FIRST BRITISH STANDARD FOR ON-LOAD TAP-CHANGERS
    ABDY, CA
    ELECTRICAL REVIEW, 1970, 186 (13): : 465 - &
  • [9] Detection of Defects in On-Load Tap-Changers Using Acoustic Emission Method
    Cichon, Andrzej
    Fracz, Pawel
    Boczar, Tomasz
    Zmarzly, Dariusz
    CONFERENCE RECORD OF THE 2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2012, : 184 - 188
  • [10] A Review of Fault Diagnosis Research on On-Load Tap-Changers
    Jin, Liang
    Cai, Yuqi
    2019 THE 2ND INTERNATIONAL SYMPOSIUM ON HYDROGEN ENERGY AND ENERGY TECHNOLOGIES (HEET 2019), 2020, 155