Ventilation performance and indoor air quality in workstations under different supply air systems: A numerical approach

被引:6
|
作者
Jiang, Z
Haghighat, F
Chen, Q
机构
[1] Building Technology, Department of Architecture, Massachusetts Inst. of Technology, Cambridge, MA
[2] Centre for Building Studies, Concordia University, Montreal, Que.
[3] Centre for Building Studies, Concordia University, 1455 de Maisonneuve Blvd. W, Montreal
关键词
ventilation; indoor air quality; computational fluid dynamics; numerical approach; workstation;
D O I
10.1177/1420326X9700600306
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper describes the results of a computational fluid dynamics study to assess the air freshness and percentage of dissatisfied people due to air quality in a partitioned office with different supply air diffusers. The numerical model involves the finite-volume approach of solving governing equations for mass and momentum, assuming that the buoyancy effects are negligibly small in comparison to the inertial effects. The IC-E two-equation model of turbulence is used to predict the turbulence transport of flow properties. Two typical layouts that provide six individual workstations are studied. The results show that for displacement ventilation and wall jet diffusers, with the exhaust opening placed on the wall opposite to the supply opening, arranging chambers in the central area of the office may be better. When the exhaust opening is placed on the same wall as the supply diffuser, arranging chambers near side walls may be more favourable. The ceiling-mounted four-way diffuser is found to be more suitable for a partitioned office than the wall jet and displacement diffusers.
引用
收藏
页码:160 / 167
页数:8
相关论文
共 50 条
  • [41] Effects of Ventilation and Air Cleaning on Indoor Air Quality of a Swimming Pool - Mass Balance Analysis Approach
    Lee, Chang-Seo
    Lakdawala, Ness
    Haghighat, Fariborz
    SEVENTH INTERNATIONAL COLD CLIMATE HVAC CONFERENCE, 2012, : 152 - 160
  • [42] Numerical investigation of indoor air quality in a floor heated room with different air change rates
    Mustafa Mutlu
    Building Simulation, 2020, 13 : 1063 - 1075
  • [43] Numerical investigation of indoor air quality in a floor heated room with different air change rates
    Mutlu, Mustafa
    BUILDING SIMULATION, 2020, 13 (05) : 1063 - 1075
  • [44] Control of Different Parameters for Indoor Air Quality Management through Natural Ventilation
    Pepe, Crescenzo
    Farooq, Ali Mir
    Zanoli, Silvia Maria
    2024 25TH INTERNATIONAL CARPATHIAN CONTROL CONFERENCE, ICCC 2024, 2024,
  • [45] Numerical Simulation on Indoor Air Pollution Diffusion and Ventilation
    Li, Dong
    Zhao, Yan
    Wu, Guozhong
    COMPUTER SCIENCE FOR ENVIRONMENTAL ENGINEERING AND ECOINFORMATICS, PT 2, 2011, 159 : 13 - 17
  • [46] Modeling the performance of personalized ventilation under different conditions of room air and personalized air
    Gao, NP
    Niu, JL
    HVAC&R RESEARCH, 2005, 11 (04): : 587 - 602
  • [47] Ventilation for better indoor air quality - Selected papers from the Indoor Air 2005 Conference
    Department of Mechanical Engineering, The University of Hongkong, Hongkong, Hong Kong
    不详
    Int. J. Vent., 2006, 3 (273):
  • [48] Improving the indoor air quality using the individual air supply system
    Zender-Swiercz, E.
    INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2018, 15 (04) : 689 - 696
  • [49] Improving the indoor air quality using the individual air supply system
    E. Zender-Świercz
    International Journal of Environmental Science and Technology, 2018, 15 : 689 - 696
  • [50] Influence of indoor air quality on energy performance of HVAC systems
    Kajtar, Laszlo
    Hrustinszky, Tamas
    PROCEEDINGS OF THE 6TH IASME/WSEAS INTERNATIONAL CONFERENCE ON HEAT TRANSFER, THERMAL ENGINEERING AND ENVIRONMENT (HTE'08), PTS I AND II: NEW ASPECTS OF HEAT TRANSFER, THERMAL ENGINEERING AND ENVIRONMENT, 2008, : 360 - +