Multicycle Incipient Fault Detection and Location for Medium Voltage Underground Cable

被引:64
|
作者
Zhang, Wenhai [1 ]
Xiao, Xianyong [1 ]
Zhou, Kai [1 ]
Xu, Wilsun [2 ]
Jing, Yindi [2 ]
机构
[1] Sichuan Univ, Coll Elect Engn & Informat Technol, Chengdu 610065, Peoples R China
[2] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 1H9, Canada
关键词
Multi-cycle incipient fault; arcing fault; fault detection; fault location; medium voltage underground cable; TRANSIENT DISTURBANCES; DISTRIBUTION-SYSTEMS; ARCING FAULTS; ALGORITHM; AUTORECLOSURE; SIMULATION;
D O I
10.1109/TPWRD.2016.2615886
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Early and accurate detection of incipient cable faults is of a great interest to the utility industry. Such faults can be classified into subcycle and multicycle types. Although a lot of research has been conducted on subcycle types of faults, little work has been done for multicycle types of faults. This paper proposes a novel method for detecting and locating a multicycle incipient fault in a cable. The incipient fault is modeled as a self-clearing arcing fault. The distortion degree of calculated voltage is used to detect the occurrence of an incipient fault. The degree of match between the measured and calculated waveforms is used to guide the search for the fault distance. The accuracy is further improved by taking into account the incipient fault angle as seen in the voltage waveform and the power loss characteristics. The proposed method has been verified by PSCAD/EMTDC simulations. Lab experiments are also conducted to further validate the proposed detection method.
引用
收藏
页码:1450 / 1459
页数:10
相关论文
共 50 条
  • [32] EXPERIENCE WITH MODERN HIGH VOLTAGE CABLE FAULT LOCATION METHODS
    BOLTON, KGW
    [J]. ELECTRICAL REVIEW, 1970, 187 (14): : 477 - &
  • [33] Cable Fault Location in High Voltage Cables - A New Solution
    Boehme, F.
    Pietsch, R.
    Kaltenborn, U.
    Hensel, M.
    [J]. 2019 IEEE PES GTD GRAND INTERNATIONAL CONFERENCE AND EXPOSITION ASIA (GTD ASIA), 2019, : 406 - 410
  • [34] Analysis of Characteristic Quantity of Incipient Fault of Medium Voltage Cable Joints in Water-Logged Environment Based on Fluid Characteristics
    Yu, Zhipeng
    Xu, Yongpeng
    Liu, Yadong
    Yan, Yingjie
    Jiang, Xiuchen
    Wang, Ke
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2024, 73
  • [35] Incipient Fault Location Method of Cable Based on Both-End Electric Quantities
    Pan, Wenxia
    Li, Ye
    Sun, Kai
    Zhu, Zhu
    Li, Xinrui
    [J]. IEEE ACCESS, 2020, 8 : 219503 - 219512
  • [36] Weather and Seasonal Effects on Medium Voltage Underground Cable Joint Failures
    Alhusin, Mohammed Omer
    Sahoo, Animesh
    Nikolakakos, Iraklis
    Alhammadi, Hassan
    Alsahi, Ahmed
    Alhammadi, Mohamed
    [J]. 2022 IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2022 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2022,
  • [37] Computation of the Electric Field in Aged Underground Medium Voltage Cable Insulation
    Stancu, C.
    Notingher, P. V.
    Notingher, P., Jr.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (05) : 1530 - 1539
  • [38] CURRENT TRENDS IN MEDIUM VOLTAGE PRIMARY UNDERGROUND POWER CABLE.
    Raikos, George
    [J]. Wire Journal International, 1988, 21 (08):
  • [39] Detection and Location of Single Cable Fault by Impedance Spectroscopy
    Shi, Qinghai
    Kanoun, Olfa
    [J]. 2014 IEEE INTERNATIONAL INSTRUMENTATION AND MEASUREMENT TECHNOLOGY CONFERENCE (I2MTC) PROCEEDINGS, 2014, : 595 - 599
  • [40] Aircraft Cable Fault Location Based on Detection Model
    Liu, Xiaolin
    Li, Zhiquan
    [J]. RECENT TRENDS IN MATERIALS AND MECHANICAL ENGINEERING MATERIALS, MECHATRONICS AND AUTOMATION, PTS 1-3, 2011, 55-57 : 332 - 336