Evaluation of breakdown characteristics of oil-immersed transformers under non-standard lightning impulse waveforms - Definition of non-standard lightning impulse waveforms and insulation characteristics for waveforms including pulses

被引:29
|
作者
Okabe, Shigemitsu [1 ]
机构
[1] Tokyo Elect Power Co Ltd, High Voltage & Insulat Grp, R&D Ctr, Tsurumi Ku, Yokohama, Kanagawa 2308510, Japan
关键词
oil-immersed transformer; non-standard lightning impulse voltage waveform; dielectric breakdown voltage; partial discharge inception voltage; oil gap; turn-to-turn insulation model; section-to-section insulation model; lightning impulse; withstand voltage;
D O I
10.1109/TDEI.2007.302883
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To lower the insulation specifications (specifically, the lightning impulse withstand voltage) of oil-immersed transformers and thus cut the equipment cost while maintaining the high reliability in its insulation performance, it is necessary to grasp in an organized way the insulation characteristics under non-standard lightning impulse voltage waveforms that represent actual surge waveforms encountered in the field and compare them with the characteristics under the standard lightning impulse waveform quantitatively. As described in this paper, the first step in a series of study for the purpose above was taken by analyzing lightning surge waveforms and restriking surge waveforms such as disconnector switching surge waveforms at UHV, 500 kV, and 275 kV substations and identifying four typical non-standard lightning impulse waveforms with basic frequencies of 0.24 to 1.0 MHz. Then, two of these non-standard lightning impulse waveforms, the single-pulse waveform which is the most basic type and the waveform with a pulse in the crest and a subsequent flat section, were used to measure the breakdown voltage and the partial discharge inception voltage while changing the parameters, on three models that represent the insulation elements of windings of oil-immersed transformers. Then, the resultant average breakdown voltages were evaluated in terms of the overvoltage durations, leading to a result of formulating them in a unified way. In the tested range, the dielectric breakdown values under nonstandard lightning impulse waveforms were higher, marking 52% at the maximum, than those under standard lightning impulse waveforms in all the cases, suggesting a possibility of lowering the insulation specifications of an oil-immersed transformer.
引用
收藏
页码:146 / 155
页数:10
相关论文
共 50 条
  • [31] Modified disruptive effect method as a measure of insulation strength for non-standard lightning waveforms
    Savadamuthu, U
    Udayakumar, K
    Jayashankar, V
    IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (02) : 510 - 515
  • [32] The effects of non-standard lightning impulse on electrical insulation: a review
    Ghosh, Pradipta
    Das, Arup Kumar
    Dalai, Sovan
    Chatterjee, Saibal
    ELECTRICAL ENGINEERING, 2022, 104 (06) : 4239 - 4254
  • [33] The effects of non-standard lightning impulse on electrical insulation: a review
    Pradipta Ghosh
    Arup Kumar Das
    Sovan Dalai
    Saibal Chatterjee
    Electrical Engineering, 2022, 104 : 4239 - 4254
  • [34] A Method for Representing Non-Standard Waveform in Factory Tests Using Impulse Waveforms
    Wickert, Humberto Margel
    Marchesan, Tiago Bandeira
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 3491 - 3500
  • [35] Generation of Non-standard Lightning Impulse Unipolar Waveshapes
    Shigihara, M.
    Piantini, A.
    Braz, C. P.
    da Silva, D. A.
    Kodaira, C. Y.
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [36] Insulation Characteristics and Its Evaluation Method of N2 Gas for Nonstandard Lightning Impulse Waveforms
    Kaneko, Shuhei
    Okabe, Shigemitsu
    ELECTRICAL ENGINEERING IN JAPAN, 2009, 167 (02) : 10 - 20
  • [37] Effect of Waveform on Breakdown Characteristics of Oil-paper Insulation Under Double-exponential Non-standard Lightening Impulse
    Ni H.
    Zhang Q.
    Zhao Y.
    Liu X.
    Guo C.
    Guo N.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (03): : 743 - 750
  • [38] Insulation Characteristics of Oil-immersed Power Transformer under Lightning Impulse and AC Superimposed Voltage
    Ueta, Genyo
    Tsuboi, Toshihiro
    Takami, Jun
    Okabe, Shigemitsu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (03) : 1384 - 1392
  • [39] Breakdown behavior of rod-rod short air gaps under non-standard lightning impulse voltage
    Xie, Jianmin
    Qiu, Yuchang
    Mazzetti, C.
    Gaoya Dianqi/High Voltage Apparatus, 2000, 36 (05): : 6 - 8
  • [40] Breakdown Characteristics of Gas-Insulated Switchgear for Nonstandard Lightning Impulse Waveforms Under Nonuniform Electric Field
    Ueta, Genyo
    Kaneko, Shuhei
    Okabe, Shigemitsu
    ELECTRICAL ENGINEERING IN JAPAN, 2011, 177 (01) : 11 - 18