Evaluation of breakdown characteristics of oil-immersed transformers under non-standard lightning impulse waveforms - Definition of non-standard lightning impulse waveforms and insulation characteristics for waveforms including pulses

被引:29
|
作者
Okabe, Shigemitsu [1 ]
机构
[1] Tokyo Elect Power Co Ltd, High Voltage & Insulat Grp, R&D Ctr, Tsurumi Ku, Yokohama, Kanagawa 2308510, Japan
关键词
oil-immersed transformer; non-standard lightning impulse voltage waveform; dielectric breakdown voltage; partial discharge inception voltage; oil gap; turn-to-turn insulation model; section-to-section insulation model; lightning impulse; withstand voltage;
D O I
10.1109/TDEI.2007.302883
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To lower the insulation specifications (specifically, the lightning impulse withstand voltage) of oil-immersed transformers and thus cut the equipment cost while maintaining the high reliability in its insulation performance, it is necessary to grasp in an organized way the insulation characteristics under non-standard lightning impulse voltage waveforms that represent actual surge waveforms encountered in the field and compare them with the characteristics under the standard lightning impulse waveform quantitatively. As described in this paper, the first step in a series of study for the purpose above was taken by analyzing lightning surge waveforms and restriking surge waveforms such as disconnector switching surge waveforms at UHV, 500 kV, and 275 kV substations and identifying four typical non-standard lightning impulse waveforms with basic frequencies of 0.24 to 1.0 MHz. Then, two of these non-standard lightning impulse waveforms, the single-pulse waveform which is the most basic type and the waveform with a pulse in the crest and a subsequent flat section, were used to measure the breakdown voltage and the partial discharge inception voltage while changing the parameters, on three models that represent the insulation elements of windings of oil-immersed transformers. Then, the resultant average breakdown voltages were evaluated in terms of the overvoltage durations, leading to a result of formulating them in a unified way. In the tested range, the dielectric breakdown values under nonstandard lightning impulse waveforms were higher, marking 52% at the maximum, than those under standard lightning impulse waveforms in all the cases, suggesting a possibility of lowering the insulation specifications of an oil-immersed transformer.
引用
收藏
页码:146 / 155
页数:10
相关论文
共 50 条