Experimental and Analytical Studies on Lightning Surge Response of 500-kV Transmission Tower

被引:32
|
作者
Motoyama, Hideki [1 ]
Kinoshita, Yasuhide
Nonaka, Katsumasa [2 ]
Baba, Yoshihiro [3 ]
机构
[1] Cent Res Inst Elect Power Ind, Yokosuka, Kanagawa 2400196, Japan
[2] Chubu Elect Power Co Inc, Nagoya, Aichi 4560022, Japan
[3] Doshisha Univ, Kyotanabe 6100321, Japan
关键词
Electromagnetic transient; finite-difference time-domain (FDTD) method; lightning; lightning outage; lightning surge; numerical electromagnetic (EM)-field analysis; tower surge response; transmission line; transmission tower; TIME; EQUATIONS;
D O I
10.1109/TPWRD.2008.2007024
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents experimental and analytical studies on the lightning surge response of a 500-kV transmission tower without overhead lines. A number of experimental studies on the lightning surge response of transmission towers have been carried out. However, in these studies, the influence of the current injection angle was ignored. In this paper, an experimental investigation is conducted to assess the influences of the angle and direction of current injection. It is clearly shown that the lightning surge response of the tower depends on the angle and direction of current injection. These experimental results are compared with results calculated using numerical electromagnetic (EM)-field analysis. These calculated results agree with the experimental results. This suggests that numerical EM-field analysis can be employed for evaluating the surge response of a tower. Based on this, the surge response of a tower under a vertical lightning stroke is estimated. It is shown that the surge response under vertical current injection is approximately 30% higher than that under horizontal current injection. It is also shown that the angle and direction of the return stroke are important factors in determining the lightning surge response of a transmission tower.
引用
收藏
页码:2232 / 2239
页数:8
相关论文
共 50 条
  • [1] Experimental study on lightning surge response of 500-kV transmission tower with overhead lines
    Motoyama, Hideki
    Kinoshita, Yasuhide
    Nonaka, Katsumasa
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 2488 - 2495
  • [2] Analytical and experimental study on surge response of transmission tower
    Motoyama, H
    Matsubara, H
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) : 812 - 819
  • [3] Analytical and experimental study on surge response of transmission tower
    Motoyama, H
    Matsubara, F
    [J]. 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, 2000, : 855 - 855
  • [4] Observation of lightning at 500-kV transmission lines (Part 1)
    [J]. Ouchi, Katsuhiro, 1600, Scripta Technica Inc, New York, NY, United States (130):
  • [5] Observation of lightning at 500-kV transmission lines (Part 1)
    Ouchi, K
    Kikuchi, TK
    Ozawa, A
    Tamura, Y
    Nakada, M
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 2000, 130 (02) : 59 - 67
  • [6] Experimental and Analytical Studies on Lightning Surge Response of the Quadruple-Circuit Transmission Line
    Zhu, Qianxin
    Zhang, Yi
    Ma, Yutang
    Zhou, Fangrong
    Yin, Hongjiang
    Zhang, Haihu
    Pan, Hao
    Geng, Hao
    Zhang, Bingzhen
    Cheng, Zhengjun
    Yu, Lei
    Qiu, Tingwei
    [J]. IEEE ACCESS, 2023, 11 : 6879 - 6886
  • [7] 500-KV TRANSMISSION IN RETROSPECT
    RAWLS, JA
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1966, PA85 (06): : 559 - &
  • [8] LIGHTNING PERFORMANCE OF TVAS 500-KV AND 161-KV TRANSMISSION-LINES
    WHITEHEAD, JT
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (03): : 752 - 768
  • [9] Development of polymeric surge ZnO arresters for 500-kV compact transmission line
    He, JL
    Chen, S
    Zeng, R
    Hu, J
    Deng, CG
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) : 113 - 120