Experimental and Analytical Studies on Lightning Surge Response of the Quadruple-Circuit Transmission Line

被引:0
|
作者
Zhu, Qianxin [1 ]
Zhang, Yi [1 ]
Ma, Yutang [2 ]
Zhou, Fangrong [2 ]
Yin, Hongjiang [1 ]
Zhang, Haihu [1 ]
Pan, Hao [2 ]
Geng, Hao [2 ]
Zhang, Bingzhen [1 ]
Cheng, Zhengjun [1 ]
Yu, Lei [1 ]
Qiu, Tingwei [1 ]
机构
[1] Yunnan Power Grid Co Ltd, Yuxi Power Supply Bur, Yuxi 653100, Yunnan, Peoples R China
[2] Yunnan Power Grid Co Ltd, Elect Power Res Inst, Kunming 650200, Yunnan, Peoples R China
关键词
FDTD; lightning protection; lightning surge response; quadruple-circuit tower; reduced-scale experiment; TOWER MODEL;
D O I
10.1109/ACCESS.2023.3237780
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The compact design of a 500 kV quadruple-circuit transmission line can effectively reduce the line corridor area, but the height of the tower also increases, increasing the probability of suffering a lightning strike. The 500 kV quadruple-circuit transmission lines carry more energy, and because of this, lightning strikes that cause power line trips are more likely to result in large-scale power outages. Therefore, it is necessary to make an accurate assessment of the lightning performance of 500 kV quadruple-circuit transmission lines. First, simulated lightning-striking experiments were carried out on a scaled 500 kV quadruple-circuit transmission line in the laboratory, where transient voltages and currents were measured. Second, a numerical model was established with the Finite-Difference Time Domain (FDTD) method, which was then verified with the experimental results. Third, lightning surge responses of a 500 kV quadruple-circuit transmission line under near-real facility conditions are estimated with the verified FDTD model. In the simulations, influencing factors, such as the rise time of injecting current, the velocity of return-stroke current and the terrains, were taken into consideration, but not in previous lightning surge analysis with the Electromagnetic Transients Program (EMTP). Results show that insulator voltages on the same tower cross-arm are nearly identical, although the length of the cross-arm is large enough. Furthermore, it is found that the rise time and the lightning current velocity have great effects on the lightning surge response, and the terrains are less impactful but not negligible. Therefore, these factors should be considered carefully where higher accuracy lightning protection design is necessary.
引用
收藏
页码:6879 / 6886
页数:8
相关论文
共 50 条
  • [1] Studying of Lightning Surge Transient Effect on 500 kV Quadruple Circuit Transmission Line
    Kusuma, Aristo Adi
    Pramana, Putu Agus Aditya
    Munir, Buyung S.
    Ayu, Rica S.
    [J]. 2016 6TH INTERNATIONAL ANNUAL ENGINEERING SEMINAR (INAES), 2016, : 276 - 279
  • [2] Experimental and Analytical Studies on Lightning Surge Response of 500-kV Transmission Tower
    Motoyama, Hideki
    Kinoshita, Yasuhide
    Nonaka, Katsumasa
    Baba, Yoshihiro
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) : 2232 - 2239
  • [3] ASSESSMENT OF THE LIGHTNING PERFORMANCE OF QUADRUPLE-CIRCUIT TRANSMISSION-LINES WITH STEEL AND WOODEN CROSSARMS
    LIEW, AC
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1993, 27 (02) : 91 - 97
  • [4] Lightning performances for AC 500kV transmission lines with quadruple-circuit on single tower
    Chai, Yajing
    Zhou, Wenjun
    Xue, Li
    Liu, Xiaodong
    Su, Hongmei
    [J]. 2007 COMPATIBILITY IN POWER ELECTRONICS, 2007, : 83 - 88
  • [5] Assessment of Lightning Backflash Outage Rate of Quadruple-circuit Transmission Lines due to Subsequent Strokes
    Huang, Bo
    Fu, Zhengcai
    Jiang, Anfeng
    Wang, Guoli
    Li, Ruihai
    [J]. 2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 917 - 921
  • [6] COMPARATIVE-STUDIES OF LIGHTNING PERFORMANCE OF A QUADRUPLE-CIRCUIT DUAL VOLTAGE 275 132KV TRANSMISSION-LINE DESIGN WITH WOODEN CROSSARMS
    LIEW, AC
    THUM, PC
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (04) : 1973 - 1980
  • [7] Lightning performance and its prevention for quadruple-circuit transmission line with 220kV/110kV voltage in a tower
    [J]. Chunhua, L. (sjyouxiang@sohu.com), 1600, Universitas Ahmad Dahlan, Jalan Kapas 9, Semaki, Umbul Harjo,, Yogiakarta, 55165, Indonesia (11):
  • [8] Shielding failure lightning protection of 500kV quadruple-circuit transmission lines on the same tower
    Yu, Shifeng
    Ruan, Jiangjun
    [J]. 2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 1705 - 1708
  • [9] Lightning protection performance of quadruple-circuit 500 kV transmission lines on the same tower with composite cross arm
    Li, Haichen
    Xiang, Nianwen
    Bao, Hua
    Jin, Miao
    Ding, Lijian
    [J]. ENERGY REPORTS, 2022, 8 : 520 - 526
  • [10] A New Approach to Measure the Distributed Parameters of Quadruple-Circuit Transmission Lines
    Hu, Zhijian
    Ni, Shiyuan