An Investigation on Cooling Performance of Air-Cooled Heat Exchangers Used in Coal Seam Gas Production

被引:4
|
作者
Lu, Yuanshen [1 ,2 ]
Guan, Zhiqiang [1 ,2 ]
Hooman, Kamel [1 ,2 ]
Parulekar, Prashant S. [3 ]
机构
[1] Queensland Geothermal Energy Ctr Excellence, St Lucia, Qld, Australia
[2] Univ Queensland, Sch Mech & Min Engn, Mansergh Shaw Bldg 45,Cooper Rd, St Lucia, Qld 4072, Australia
[3] Arrow Energy, Brisbane, Qld, Australia
关键词
INTAKE FLOW-RATE; WIND; TOWER;
D O I
10.1080/01457632.2016.1217039
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper reports an investigation into a practical cooling issue on a type of fan-forced finned-tube heat exchangers used in Queensland's coal seam gas (CSG) industry. CSG compression facilities in some production sites suffered underproduction in recent summers because of frequent automatic engine shutdowns. The problem is not expected by the manufacturer's design. However, it is suspected of being related to the control systems on the compression facilities triggering the overheating-protection shutdowns due to possible deficiencies in one or some water/gas cooling loops in the facilities' air-cooled heat exchangers. Therefore, to understand which heat exchangers and what exact reasons cause the unexpected cooling issue, an investigation has been carried out on the cooler units of the gas compression facilities. A field instrumentation measurement on one operating cooler unit has been done, followed by an analysis using a one-dimensional analytical model and a three-dimensional computational fluid dynamics model. The experimental results are used to validate both the models. Then the cooling performance of the cooler unit under the summer peak condition is predicted by the verified models. The prediction suggests that the water inlet temperature in one particular cooler section is higher than its upper limit defined by the manufacturer, due to poor cooling at high ambient temperatures. The lower cooling performance is caused by large reductions in the cooler air speed and total heat transfer coefficient, which are related to less efficiency of the cooler fans, more airflow resistance, and fouling on both sides of the finned tubes.
引用
收藏
页码:1073 / 1088
页数:16
相关论文
共 50 条
  • [41] FINNED ELLIPTICAL TUBES AND THEIR APPLICATION IN AIR-COOLED HEAT EXCHANGERS
    SCHULENBERG, FJ
    JOURNAL OF ENGINEERING FOR INDUSTRY, 1966, 88 (02): : 179 - +
  • [42] DESIGN AND OPTIMIZATION OF AIR-COOLED HEAT-EXCHANGERS - CLOSURE
    HEDDERICH, CP
    KELLEHER, MD
    VANDERPLAATS, GN
    JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1984, 106 (01): : 256 - 256
  • [44] Experimental and numerical investigation of using pulsating heat pipes instead of fins in air-cooled heat exchangers
    Mosleh, Hassan Jafari
    Bijarchi, Mohamad Ali
    Shafii, Mohammad Behshad
    ENERGY CONVERSION AND MANAGEMENT, 2019, 181 : 653 - 662
  • [45] Energy efficiency and performance considerations of variable frequency drives for air-cooled heat exchangers
    Endrejat, F
    van Niekerk, HR
    Delport, GJ
    IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE 98) - PROCEEDINGS, VOLS 1 AND 2, 1998, : 312 - 316
  • [46] NUMERICAL INVESTIGATION OF THE PERFORMANCE OF A FORCED DRAFT AIR-COOLED HEAT EXCHANGER
    Engelbrecht, Ruan A.
    Van der Spuy, Johan
    Meyer, Chris J.
    Zapke, Albert
    PROCEEDINGS OF THE ASME TURBO EXPO: TURBINE TECHNICAL CONFERENCE AND EXPOSITION, 2017, VOL 5A, 2017,
  • [47] PERFORMANCE OF AIR-COOLED POWER PLANTS USING GAS FROM COAL.
    Anon
    Electric Power Research Institute, Advanced Power Systems Division, (Report) EPRI AP, 1981,
  • [48] Numerical investigation of the temporal evolution of particulate fouling in metal foams for air-cooled heat exchangers
    Kuruneru, Sahan Trushad Wickramasooriya
    Sauret, Emilie
    Saha, Suvash Chandra
    Gu, YuanTong
    APPLIED ENERGY, 2016, 184 : 531 - 547
  • [49] Enhance air-cooled heat exchanger performance
    Shastri, SS
    Karimi, IA
    Rangaiah, GP
    Yap, C
    HYDROCARBON PROCESSING, 2001, 80 (12): : 49 - +
  • [50] Optimize air-cooled heat exchanger performance
    Agius, N.
    HYDROCARBON PROCESSING, 2006, 85 (07): : 89 - +