Influence of Air Pressure on Positive DC Corona Inception Voltage of Stranded Conductors in the Corona cage

被引:0
|
作者
Meng, Xiaobo [1 ,2 ]
Bian, Xingming [1 ,2 ]
Chen, Fenglin [1 ,2 ]
Yang, Yingjian [3 ]
Wang, Liming [1 ,2 ]
Guan, Zhicheng [1 ,2 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, Beiijing 100084, Peoples R China
[2] Tsinghua Univ, Grad Sch Shenzhen, Shenzhen 518055, Peoples R China
[3] State Grid Elect Power Res Inst, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
positive DC corona; inception voltage; air pressure; corona cage; stranded conductors; ONSET VOLTAGE; AVAILABILITY; PERFORMANCE;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The transmission lines pass by the high altitude region with low air pressure, which brings many special problems to the design and operation of the transmission lines. The corona cage is widely used to study the corona performance of conductors for its good economy and maneuverability. A computation model is adopted for evaluating the corona inception voltages of conductors in the corona cage, which is established according to the gas discharge theory. The charge simulation method is introduced to the computation model to calculate the electric field intensity. Then the positive corona inception voltage are calculated according to the positive corona criterion. The influence of air pressure on the corona inception voltage of conductors is analysed systematically. Corona inception voltage decreases as air pressure is lowered. The corona inception voltage may decrease by 9% per 0.01MPa bases on the standard atmospheric pressure, which is mainly due to the enlargement of ionization zone as a result of the increase of effective ionization coefficient.
引用
收藏
页数:4
相关论文
共 50 条
  • [31] Effect of atmospheric factors on AC corona inception voltage of conductors and its correction
    Hu, Qin
    Shu, Lichun
    Jiang, Xingliang
    Sun, Caixin
    Yuan, Qianfei
    Yang, Zhangang
    Dianwang Jishu/Power System Technology, 2010, 34 (11): : 70 - 76
  • [32] Negative DC Corona Inception in Coaxial Cylinders under Variable Atmospheric Conditions: A Comparison with Positive Corona
    Mikropoulos, P. N.
    Zagkanas, V. N.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (03) : 1322 - 1330
  • [33] CORONA INCEPTION GRADIENT AND THE DELAY TIME OF THE ONSET CORONA AROUND CONDUCTORS.
    Gary, C.
    Dragan, G.
    Lungu, I.
    Buletinul Institutului Politehnic Bucuresti. Seria electrotehnica, 1987, 49 : 35 - 39
  • [34] Negative Corona Onset Characteristic of the UHV Conductors Based on the Corona Cage
    Liu, Yun-Peng
    Zhu, Lei
    Lv, Fang-Cheng
    Xie, Xiongjie
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2014, 9 (06) : 2089 - 2097
  • [35] Properties of corona discharge under positive DC voltage at low atmospheric pressure
    Yu, D.
    Farzaneh, M.
    Zhang, J.
    Shu, L.
    Sima, W.
    Sun, C.
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 393 - 396
  • [36] AC Conductors' Corona-Loss Calculation and Analysis in Corona Cage
    Lu, Fang-Cheng
    You, Shao-Hua
    Liu, Yun-Peng
    Wan, Qi-Fa
    Zhao, Zhi-Bin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) : 877 - 885
  • [37] Investigation on corona performance of conductors using fabricated indoor corona cage
    Megala, V.
    Karpagam, R.
    Sathishkumar, G. K.
    Gopinath, B.
    Kumar, P. Marish
    Brindha, M. Deva
    MATERIALS TODAY-PROCEEDINGS, 2021, 44 : 3652 - 3656
  • [38] Study of UHV DC corona performance in a mini corona cage
    Wang, Wei
    Li, Chengrong
    Fan, Jianbin
    Gu, Chen
    Jiang, Yitao
    Cui, Guohua
    2007 ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING EXPO, 2007, : 459 - +
  • [39] A helical charge simulation based 3-D calculation model for corona loss of AC stranded conductors in the corona cage
    Liu, Yunpeng
    Huang, Shilong
    Liu, Shugang
    Liu, Daran
    AIP ADVANCES, 2018, 8 (01):
  • [40] Experimental Analysis on Corona Inception Voltage of Rod-Plane Air Gaps under DC and AC Composite Voltage
    Zhang, Jinglan (haha830830@126.com), 1600, China Machine Press (32):