Analysis of indoor air parameters in an education building

被引:15
|
作者
Krawczyk, Dorota A. [1 ]
Wadolowska, Bernadetta [2 ]
机构
[1] Bialystok Tech Univ, Dept HVAC Engn, Wiejska 45A, PL-15351 Bialystok, Poland
[2] Bialystok Tech Univ, Wiejska 45A, PL-15351 Bialystok, Poland
关键词
indoor air quality; CO2; air chage rates; temperature; CO2; CONCENTRATION; QUALITY; SCHOOLS; MICROCLIMATE; VENTILATION; CLASSROOMS; ENVIRONMENT; POLLUTANT; OUTDOOR; CLIMATE;
D O I
10.1016/j.egypro.2018.07.038
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Main parameters of IAQ (indoor air quality) could influence people health as well as their ability to learning and work. This research on IAQ was conducted in a classroom of Bialystok University of Technology located in the north-eastern part of Poland. We focused on issues related to indoor temperature, relative humidity, carbon dioxide concentration, air change rates and noise. Indoor temperature was recorded in a range from 23.1 degrees C to 24.9 degrees C, so higher than design temperature set at 20 degrees C or comfort temperature found as average 22 degrees C [1]. On the other hand, relative humidity was slightly lower than recommended minimum 40 % (range 31.7 % to 38.3 %). Moreover, we found that the concentration of carbon dioxide during the experiment was constantly increasing to final 1067 ppm, while the average air exchange rate was 1.5 h(-1). (C) 2018 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:96 / 103
页数:8
相关论文
共 50 条
  • [1] Measuring and analysis of indoor air quality of building
    Li, DY
    Deng, QQ
    Pan, SY
    Hao, XJ
    Shi, YZ
    2ND ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, PROCEEDINGS: NEW CONTRIBUTION TO ASIAN SUSTAINABLE DEVELOPMENT, 2004, : 627 - 633
  • [2] Study on Indoor Air Quality in the Education Building Teaching Space
    Xu, Xiaokun
    Yan, Zengfeng
    PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 1: INDOOR AND OUTDOOR ENVIRONMENT, 2014, 261 : 175 - 184
  • [3] Analysis of the impact of the parameters of outside air on the condition of indoor air
    E. Zender – Świercz
    International Journal of Environmental Science and Technology, 2017, 14 : 1583 - 1590
  • [4] Analysis of the impact of the parameters of outside air on the condition of indoor air
    Zender-Swiercz, E.
    INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2017, 14 (08) : 1583 - 1590
  • [5] Assessment of Indoor Air Parameters in Building Equipped with Decentralised Facade Ventilation Device
    Zender-Swiercz, Ewa
    ENERGIES, 2021, 14 (04)
  • [6] Analysis of the Importance of Fresh Air System to Indoor Environment of Green Building and Healthy Building
    Chen Xiaoyi
    Niu Runping
    Liu Hua
    Yu Kai
    2020 6TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY, ENVIRONMENT AND CHEMICAL ENGINEERING, PTS 1-5, 2020, 546
  • [7] Indoor air quality of a hospital building
    Myojo, Toshihiko
    Oyabu, Takako
    Lee, Byeong Woo
    Okada, Takami
    Ishimatsu, Sumiyo
    Matsuu, Satomi
    29TH SYMPOSIUM ON AEROSOL SCIENCE AND TECHNOLOGY, 2012, 2012, : 219 - 220
  • [8] INFLUENCE OF AIR SUPPLY PARAMETERS ON INDOOR AIR DIFFUSION
    CHEN, QY
    SUTER, P
    MOSER, A
    BUILDING AND ENVIRONMENT, 1991, 26 (04) : 417 - 431
  • [9] BUILDING VENTILATION AND INDOOR AIR-QUALITY
    BERK, JV
    AMERICAN CERAMIC SOCIETY BULLETIN, 1980, 59 (03): : 327 - 327
  • [10] Indoor air sciences education in Slovakia
    Senitkova, I
    PROCEEDINGS OF THE SECOND NSF INTERNATIONAL CONFERENCE ON INDOOR AIR HEALTH: TRENDS AND ADVANCES IN RISK ASSESSMENT AND MANAGEMENT, 2001, : 217 - 223