An experimental study on a full-scale indoor thermal environment using an Under-Floor Air Distribution system

被引:25
|
作者
Lin, Y. J. P. [1 ]
Tsai, T. Y. [1 ]
机构
[1] Natl Taiwan Univ Sci & Technol, Dept Mech Engn, Taipei 106, Taiwan
基金
美国国家科学基金会;
关键词
Under-Floor Air Distribution (UFAD) system; Vertical temperature profile; Stratification height; Throw height; Jet flow; Gravity current; ENERGY; STRATIFICATION; VENTILATION; BUILDINGS;
D O I
10.1016/j.enbuild.2014.05.028
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Characteristics of thermal environment in a full-scale indoor space utilizing an Under-Floor Air Distribution (UFAD) system are investigated by conducting and analyzing experimental measurements. The indoor air stratification of different locations in the steady state for three supply flow rate options is presented. This research focuses on the influence of supply air flow rate, and its corresponding momentum and buoyancy fluxes, on the vertical temperature profile in the indoor environment. Temperature measurements show that the indoor vertical temperature profile is influenced highly by the distance away from the supply diffuser position. Experimental results also show that the supply air flow rate has a strong effect on the vertical temperature profile. When the supply air flow rate of a given diffuser increases, and then the supply air momentum flux increases as well, the gradient of the vertical temperature profile becomes gentler. The stratification height in the indoor environment ascends with a higher total flow rate. The almost same throw height at the supply diffuser is observed for the identical flow rate option in two sets of experiments with different total flow rates. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:321 / 330
页数:10
相关论文
共 50 条
  • [21] Vibration serviceability of suspended floor: Full-scale experimental study and assessment
    Lv, Qingfang
    Lu, Yujie
    Liu, Ye
    STRUCTURES, 2021, 34 : 1651 - 1664
  • [22] A techno-economical study of a solar-assisted under-floor air distribution system for buildings in the tropics
    Yau, Yat Huang
    Poh, Kai Sin
    Badarudin, Ahmad
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2022, 51
  • [23] An experimental study of full-scale open floor plan enclosure fires
    Hidalgo, J. P.
    Cowlard, A.
    Abecassis-Empis, C.
    Maluk, C.
    Majdalani, A. H.
    Kahrrnann, S.
    Hilditch, R.
    Krajcovic, M.
    Torero, J. L.
    FIRE SAFETY JOURNAL, 2017, 89 : 22 - 40
  • [24] Experimental study of radiation and free convection in an enclosure with under-floor heating system
    Rahimi, Mostafa
    Sabernaeemi, Arnir
    ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (07) : 2752 - 2757
  • [25] Uniformity of Supply Air in the Plenum for Under-Floor Air Distribution Ventilation in a Circular Conference Room: A CFD Study
    Fan, Xiaolei
    Yu, Tao
    Liu, Peng
    Li, Xiangdong
    ENERGIES, 2022, 15 (17)
  • [26] Performance Study of an Under-floor Air Distribution System in an Education Building to Identify Building Energy Efficiency Improvement Opportunities
    Zhao, Juan
    Khmelenko, Vasiliy
    Claridge, David
    ASHRAE TRANSACTIONS 2014, VOL 120, PT 2, 2014, 120
  • [27] Experimental study on resuspension characteristics of inhalable particles in under floor air distribution system
    Li, Can
    Li, Nianping
    Zhou, Xingling
    Wang, Meixia
    Yao, Guocai
    FIRST INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT, PROCEEDINGS VOLS 1-3, 2008, : 733 - 738
  • [28] Experimental study of under-floor electric heating system with shape-stabilized PCM plates
    Lin, KP
    Zhang, YP
    Xu, X
    Di, HF
    Yang, R
    Qin, PH
    ENERGY AND BUILDINGS, 2005, 37 (03) : 215 - 220
  • [29] Numerical study of circular jet diffuser for task ventilation of under-floor air supply system in tropics
    Yang, Bin
    Sekhar, S. C.
    BUILDING SIMULATION 2007, VOLS 1-3, PROCEEDINGS, 2007, : 1021 - 1026
  • [30] Experimental study of under-floor electric heating system with shape-stabilized PCM plates
    Lin, K
    Zhang, Y
    Xu, X
    Di, H
    Qin, R
    Yang, R
    PROCEEDINGS OF THE 4TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS 1 AND 2, 2003, : 646 - 652