An experimental study on a full-scale indoor thermal environment using an Under-Floor Air Distribution system

被引:25
|
作者
Lin, Y. J. P. [1 ]
Tsai, T. Y. [1 ]
机构
[1] Natl Taiwan Univ Sci & Technol, Dept Mech Engn, Taipei 106, Taiwan
基金
美国国家科学基金会;
关键词
Under-Floor Air Distribution (UFAD) system; Vertical temperature profile; Stratification height; Throw height; Jet flow; Gravity current; ENERGY; STRATIFICATION; VENTILATION; BUILDINGS;
D O I
10.1016/j.enbuild.2014.05.028
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Characteristics of thermal environment in a full-scale indoor space utilizing an Under-Floor Air Distribution (UFAD) system are investigated by conducting and analyzing experimental measurements. The indoor air stratification of different locations in the steady state for three supply flow rate options is presented. This research focuses on the influence of supply air flow rate, and its corresponding momentum and buoyancy fluxes, on the vertical temperature profile in the indoor environment. Temperature measurements show that the indoor vertical temperature profile is influenced highly by the distance away from the supply diffuser position. Experimental results also show that the supply air flow rate has a strong effect on the vertical temperature profile. When the supply air flow rate of a given diffuser increases, and then the supply air momentum flux increases as well, the gradient of the vertical temperature profile becomes gentler. The stratification height in the indoor environment ascends with a higher total flow rate. The almost same throw height at the supply diffuser is observed for the identical flow rate option in two sets of experiments with different total flow rates. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:321 / 330
页数:10
相关论文
共 50 条
  • [1] THERMAL COMFORT AND IEQ ASSESSMENT OF AN UNDER-FLOOR AIR DISTRIBUTION SYSTEM
    Ioan, Bode Florin
    Verona, Croitoru Cristiana
    Madalin, Dogeanu Angel
    Ilinca, Nastase
    BUILDING SIMULATION 2013: 13TH INTERNATIONAL CONFERENCE OF THE INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION, 2013, : 2334 - 2339
  • [2] Indoor air quality and thermal comfort studies of an under-floor air-conditioning system in the tropics
    Sekhar, SC
    Ching, CS
    ENERGY AND BUILDINGS, 2002, 34 (05) : 431 - 444
  • [3] Thermal comfort and indoor air quality in rooms with integrated personalized ventilation and under-floor air distribution systems
    Li, Ruixin
    Sekhar, S. C.
    Melikov, A. K.
    HVAC&R RESEARCH, 2011, 17 (05): : 829 - 846
  • [4] Effect of air change rate upon indoor inhalable particles concentration in under-floor distribution system
    Li, Can
    Li, Nian-Ping
    Yao, Guo-Cai
    Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences, 2007, 34 (12): : 26 - 29
  • [5] The Relation Between Airflow Pattern and Indoor Air Quality in a Hybrid Personalized Ventilation with Under-Floor Air Distribution System
    Rahmati, B.
    Heidarian, A.
    Jadidi, A. M.
    EXPERIMENTAL TECHNIQUES, 2023, 47 (01) : 167 - 186
  • [6] An experimental study on the indoor environment using UnderFloor Air Distribution system
    Tsai, Ting-Ya
    Liou, Ren-Hao
    Lin, Yi-Jiun Peter
    37TH NATIONAL CONFERENCE ON THEORETICAL AND APPLIED MECHANICS (37TH NCTAM 2013) & THE 1ST INTERNATIONAL CONFERENCE ON MECHANICS (1ST ICM), 2014, 79 : 263 - 266
  • [7] The Relation Between Airflow Pattern and Indoor Air Quality in a Hybrid Personalized Ventilation with Under-Floor Air Distribution System
    B. Rahmati
    A. Heidarian
    A.M Jadidi
    Experimental Techniques, 2023, 47 : 167 - 186
  • [8] Thermal comfort assessment of an office building served by under-floor air distribution (UFAD) system - A case study
    Alajmi, Ali F.
    Baddar, Faisal A.
    Bourisli, Raed I.
    BUILDING AND ENVIRONMENT, 2015, 85 : 153 - 159
  • [9] Numerical simulation for under-floor air distribution system with swirl diffusers
    Wang, Xiuling
    Pepper, Darrell W.
    JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2007, 129 (04): : 589 - 594
  • [10] Thermal environment in indoor spaces with under-floor air distribution systems: Part 1. Impact of design parameters (1522-RP)
    Lee, Kisup
    Xue, Guangqing
    Jiang, Zheng
    Chen, Qingyan
    HVAC&R RESEARCH, 2012, 18 (06): : 1182 - 1191