An Improvement of Voltage Unbalance in a Low Voltage 11/0.4 kV Electric Power distribution Network under 3-phase Unbalance Load Condition using Dynamic Voltage Restorer

被引:0
|
作者
Taiwo, Ogunboyo Patrick [1 ]
Tiako, Remy [1 ]
Davidson, Innocent E. [2 ]
机构
[1] Univ KwaZulu Natal, Elect Elect & Comp Engn Discipline, Durban, South Africa
[2] Durban Univ Technol, Dept Elect Power Engn, Durban, South Africa
关键词
unbalance voltage; power quality; low voltage; distribution network; injection voltage; dynamic voltage restorer; SAG;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The compensation of voltage unbalance disturbance in low voltage electric power distribution system using improved d-q-o and PI controller techniques is the focus of this paper. There are several methods to mitigate voltage unbalance. A very effective method of voltage unbalance compensation is the use of dynamic voltage restorer. Dynamic voltage restorer is a series-connected advanced power electronic custom-based tool. It is employed to mitigate voltage disturbances in low voltage electric power distribution network. Dynamic voltage restorer is installed in the network between the source voltage and the loads to correct voltage disturbances affecting the load voltage. This report presents the modelling of dynamic voltage restorer for voltage unbalance correction in a low voltage 11/0.4 kV electric power distribution network using MATLAB/Simulink Sim Power System tool box. Results obtained from simulation with distribution length 0.5 km to 5 km for 3-phase unbalanced loads are within the permissible nominal voltage tolerance of +/- 5% at the customer's terminal when dynamic voltage restorer is connected to the network. This is not the case when a dynamic voltage restorer is not plugged in. The results obtained demonstrate the effectiveness of this device's performance in improving voltage unbalance in a low voltage electrical power distribution from lengths 0.5 km to 5 km. The balance of the paper discusses some recommendations for an efficient, reliable and cost-effective method for improving voltage profile and reducing the voltage unbalance in 3-phase unbalance load to acceptable standards.
引用
收藏
页码:126 / 131
页数:6
相关论文
共 50 条
  • [1] Voltage Profile Enhancement in Low Voltage 11/0.4 kV Electric Power Distribution Network Using Dynamic Voltage Restorer under Three Phase Balance Load
    Taiwo, Ogunboyo Patrick
    Tiako, Remy
    Davidson, Innocent E.
    [J]. 2017 IEEE AFRICON, 2017, : 991 - 996
  • [2] Dynamic Voltage Restorer for Voltage Unbalance Mitigation and Voltage Profile Improvement in Distribution Network
    Al-karakchi, Ahmed A. Abdullah
    Albanna, Enaam
    Al-rifaie, Alya H.
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2023, 99 (06): : 188 - 191
  • [3] Effectiveness of Dynamic Voltage Restorer for Unbalance Voltage Mitigation and Voltage Profile Improvement in Secondary Distribution System
    Ogunboyo, Patrick Taiwo
    Tiako, Remy
    Davidson, Innocent E.
    [J]. CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 2018, 41 (02): : 105 - 115
  • [4] Investigation of Voltage Unbalance in Low Voltage Electric Power Distribution Network under Steady State Mode
    Taiwo, Ogunboyo Patrick
    Tiako, Remy
    Davidson, Innocent E.
    [J]. 2017 IEEE 3RD INTERNATIONAL CONFERENCE ON ELECTRO-TECHNOLOGY FOR NATIONAL DEVELOPMENT (NIGERCON), 2017, : 932 - 939
  • [5] Voltage Unbalance Mitigation and Voltage Profile Enhancement in Secondary Distribution System Using Dynamic Voltage Restorer
    Taiwo, Ogunboyo Patrick
    Tiako, Remy
    Davidson, Innocent E.
    [J]. INTERNATIONAL JOURNAL OF ENGINEERING RESEARCH IN AFRICA, 2018, 34 : 81 - 101
  • [6] A 3-phase series active power filter with compensate voltage drop and voltage unbalance
    Han, SW
    Lee, SY
    Choe, GH
    [J]. ISIE 2001: IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS PROCEEDINGS, VOLS I-III, 2001, : 1032 - 1037
  • [7] Improving network voltage unbalance levels by controlling DFIG wind turbine using a dynamic voltage restorer
    Suppioni, Vinicius P.
    Grilo, Ahda P.
    Teixeira, Julio C.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 96 : 185 - 193
  • [8] A Novel Compensator for Three-phase Load Unbalance of The Low Voltage Distribution Network
    Yin, Chunjie
    Wang, Fang
    Ding, Xudong
    Tian, Chongyi
    Duan, Peiyong
    [J]. 2017 CHINESE AUTOMATION CONGRESS (CAC), 2017, : 7518 - 7521
  • [9] Power Quality Improvement In Low Voltage Distribution System Using Dynamic Voltage Restorer (DVR)
    Omar, Rosli
    Rahim, N. A.
    [J]. ICIEA 2010: PROCEEDINGS OF THE 5TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS, VOL 2, 2010, : 408 - +
  • [10] Dynamic Voltage Regulation and Unbalance Compensation in a Low-Voltage Distribution Network Using Energy Storage System
    Rafal, Krzysztof
    Biskupski, Jacek
    Bykuc, Sebastian
    Chaja, Patryk
    [J]. APPLIED SCIENCES-BASEL, 2022, 12 (22):