Model validation and case study on internally cooled/heated dehumidifier/regenerator of liquid desiccant systems

被引:75
|
作者
Yin, Yonggao [1 ]
Zhang, Xiaosong [1 ]
Peng, Donggen [1 ]
Li, Xiuwei [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Peoples R China
基金
中国国家自然科学基金;
关键词
Liquid desiccant; Internally heated regenerator; Internally cooled dehumidifier; Optimal design; MASS-TRANSFER; HEAT; AIR; PERFORMANCE; FILM; REGENERATOR; ABSORPTION;
D O I
10.1016/j.ijthermalsci.2008.12.017
中图分类号
O414.1 [热力学];
学科分类号
摘要
Traditional dehumidifiers and regenerators of liquid desiccant systems often use packed columns supporting adiabatic heat and mass transfer between air and liquid desiccant. As new-style equipment, internally-cooled dehumidifiers can improve dehumidification performance due to restraining temperature increase of the desiccant. Similar to internally-cooled dehumidifiers, an idea of internally heating is imitated to put forward internally-heated regenerators. The uniform mathematical model for an internally cooled dehumidifier and internally heated regenerator was presented and validated by comparison of computation results with experimental data in this study. The case study focused on the parameters distribution comparisons of the internally cooled/heated dehumidifier/regenerator with adiabatic ones and demonstrated coupled heat and mass transfer behavior. The results show that the internally-heated regenerator can produce higher regeneration efficiency than the adiabatic one to produce better energy efficiency and eliminate the dehumidification possibility which would happen in adiabatic regenerators. The internally-cooled dehumidifier can also provide better dehumidification performance comparing with the adiabatic one; however its benefit would be not as good as the internally-heated regenerator. In addition, effect of the width of the air channel on internally cooled/heated dehumidifier/regenerator was discussed and the results can help the optimal design of this kind of dehumidifiers and regenerators. (C) 2008 Elsevier Masson SAS. All rights reserved.
引用
收藏
页码:1664 / 1671
页数:8
相关论文
共 50 条
  • [1] Experimental study on a new internally cooled/heated dehumidifier/regenerator of liquid desiccant systems
    Yin, Yonggao
    Zhang, Xiaosong
    Wang, Geng
    Luo, Lei
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (05): : 857 - 866
  • [2] Experimental analysis of an internally-cooled/heated liquid desiccant dehumidifier/regenerator made of thermally conductive plastic
    Liu, Jun
    Zhang, Tao
    Liu, Xiaohua
    Jiang, Jingjing
    ENERGY AND BUILDINGS, 2015, 99 : 75 - 86
  • [3] Study on an internally-cooled liquid desiccant dehumidifier with CFD model
    Luo, Yimo
    Chen, Yi
    Yang, Hongxing
    Wang, Yuanhao
    APPLIED ENERGY, 2017, 194 : 399 - 409
  • [4] Experimental and Theoretical Study of an Internally Cooled Liquid Desiccant Dehumidifier
    ZHENG Xin
    LU Yuan
    WANG Bo
    ZHAO Lifeng
    XIAO Yunhan
    Journal of Thermal Science, 2023, 32 (04) : 1684 - 1696
  • [5] Experimental and Theoretical Study of an Internally Cooled Liquid Desiccant Dehumidifier
    Xin Zheng
    Yuan Lu
    Bo Wang
    Lifeng Zhao
    Yunhan Xiao
    Journal of Thermal Science, 2023, 32 : 1684 - 1696
  • [6] Experimental and Theoretical Study of an Internally Cooled Liquid Desiccant Dehumidifier
    Zheng, Xin
    Lu, Yuan
    Wang, Bo
    Zhao, Lifeng
    Xiao, Yunhan
    JOURNAL OF THERMAL SCIENCE, 2023, 32 (04) : 1684 - 1696
  • [7] Investigation on Performance of Internally Cooled Liquid Desiccant Dehumidifier Based on ANN Model
    Luo, Yimo
    Chang, Yayin
    Li, Nianping
    Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences, 2024, 51 (09): : 198 - 205
  • [8] Experimental analysis of an internally-cooled liquid desiccant dehumidifier
    Zhang, Tao
    Liu, Xiaohua
    Jiang, Jingjing
    Chang, Xiaoming
    Jiang, Yi
    BUILDING AND ENVIRONMENT, 2013, 63 : 1 - 10
  • [9] Performance analysis on the internally cooled dehumidifier using liquid desiccant
    Liu, X. H.
    Chang, X. M.
    Xia, J. J.
    Jiang, Y.
    BUILDING AND ENVIRONMENT, 2009, 44 (02) : 299 - 308
  • [10] A study on the regeneration performance characteristics of an internally heated regenerator in a liquid desiccant system
    Ji-Hyun Mun
    Dong-Soon Jeon
    Young-Lyoul Kim
    Seon-Chang Kim
    Journal of Mechanical Science and Technology, 2016, 30 : 1343 - 1349