Analysis of the arcing process in on-load tap changers by measuring the acoustic signature

被引:0
|
作者
Bhuyan, Ranjan [1 ]
Mor, Armando Rodrigo [1 ]
Morshuis, Peter [1 ]
Montanari, Gian Carlo [2 ]
Erinkveld, Wim [3 ]
机构
[1] Delft Univ Technol, Delft, Netherlands
[2] Univ Bologna & Techimp SpA, Bologna, Italy
[3] Royal SMIT Transformers, Nijmegen, Netherlands
来源
2014 ELECTRICAL INSULATION CONFERENCE (EIC) | 2014年
关键词
acoustic detection; on-load tap changer; acoustic signature; arcing phenomenon;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power transformers are fundamental parts of the power system. In order to keep the availability of power systems high, the reliability of a transformer, in all its parts, must be assured. This requires also paying attention to the reliability of the tap changer, as tap changer failures are major causes of power transformer breakdown. This paper focuses on the development of acoustic diagnostics for on-load tap changers (OLTC). A selector switch-type tap changer was used to detect and characterize different defects that may ultimately lead to a tap changer failure. Among other techniques, acoustic diagnostic was considered first because it is a method which can work online without affecting in any way the normal operation of a power transformer. Special emphasis was dedicated to recreate the arcing conditions in a tap changer. Arcing inside the tap changer chamber is unavoidable, but excessive arcing leads to a multitude of problems, so that efforts have been made to detect acoustically the signature of the arcing phenomenon. In order to have both flexibility and control over the experimental parameters, the tests were conducted on two sets of test objects, i.e. a model and a small-size tap changer. Focus was made to the type of defects that pose the most imminent threat to the tap changer operation, and the most appropriate methods of signal acquisition and processing were singled out. It is shown that these defects can be recognized based on their specific acoustic signature.
引用
收藏
页码:193 / 197
页数:5
相关论文
共 50 条
  • [31] Dynamic analysis method for feature extraction of mechanical vibration signals of on-load tap changers
    Zhao, Tong
    Li, Qingmin
    Chen, Ping
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2007, 22 (01): : 41 - 46
  • [32] Condition assessment of power transformer on-load tap-changers using wavelet analysis
    Kang, PJ
    Birtwhistle, D
    IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (03) : 394 - 400
  • [33] On the Feasibility of Detecting Faults and Irregularities in On-Load Tap Changers (OLTCs) by Vibroacoustic Signal Analysis
    Ezzaidi, Hassan
    Fofana, Issouf
    Picher, Patrick
    Gauvin, Michel
    SENSORS, 2024, 24 (24)
  • [34] Vibration Characteristic Comparison Between Vacuum Arcing On-load Tap-changer and Oil Blast On-load Tap-changer
    Wang F.
    Fan J.
    Zheng Y.
    He W.
    Qian Y.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (09): : 2834 - 2841
  • [35] Simplified Power Flow Modeling Approach Considering On-Load Tap Changers
    Alkaabi, Sultan S.
    Zeineldin, H. H.
    Khadkikar, Vinod
    2017 IEEE POWER & ENERGY SOCIETY INNOVATIVE SMART GRID TECHNOLOGIES CONFERENCE (ISGT), 2017,
  • [36] Acoustic emission signal analysis of On-Load Tap Changer (OLTC)
    Shanker, T. Bhavani
    Nagamani, H. N.
    Punekar, Gururaj S.
    2013 IEEE 1ST INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2013, : 347 - 352
  • [37] Simplified power flow modeling approach considering on-load tap changers
    Alkaabi, Sultan S.
    Zeineldin, H.H.
    Khadkikar, Vinod
    2017 IEEE Power and Energy Society Innovative Smart Grid Technologies Conference, ISGT 2017, 2017,
  • [38] Dynamic Resistance Measurements and Result Interpretation for Various On-Load Tap Changers
    Boricic, A.
    Laban, D.
    Moedim, B.
    Lopez, A. Conde
    Molinari, B.
    Riaz, Z.
    Nikjoo, Roya
    2019 IEEE MILAN POWERTECH, 2019,
  • [39] An Improved Control Scheme for On-load Tap Changers with Reduced Harmonics Injection
    Chinthapally, Yadaiah
    Chatterjee, Debashis
    Goswami, Swapan K.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2016, 44 (07) : 794 - 805
  • [40] Comparative Analysis of Acoustic Emission Signals from On-Load Tap-Changers for Potential Detecting of Non-Simultaneous Operations
    Cichon, Andrzej
    Borucki, Sebastian
    Wlodarz, Michal
    ARCHIVES OF ACOUSTICS, 2024, 49 (02) : 277 - 286