Analysis of the arcing process in on-load tap changers by measuring the acoustic signature

被引:0
|
作者
Bhuyan, Ranjan [1 ]
Mor, Armando Rodrigo [1 ]
Morshuis, Peter [1 ]
Montanari, Gian Carlo [2 ]
Erinkveld, Wim [3 ]
机构
[1] Delft Univ Technol, Delft, Netherlands
[2] Univ Bologna & Techimp SpA, Bologna, Italy
[3] Royal SMIT Transformers, Nijmegen, Netherlands
来源
2014 ELECTRICAL INSULATION CONFERENCE (EIC) | 2014年
关键词
acoustic detection; on-load tap changer; acoustic signature; arcing phenomenon;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power transformers are fundamental parts of the power system. In order to keep the availability of power systems high, the reliability of a transformer, in all its parts, must be assured. This requires also paying attention to the reliability of the tap changer, as tap changer failures are major causes of power transformer breakdown. This paper focuses on the development of acoustic diagnostics for on-load tap changers (OLTC). A selector switch-type tap changer was used to detect and characterize different defects that may ultimately lead to a tap changer failure. Among other techniques, acoustic diagnostic was considered first because it is a method which can work online without affecting in any way the normal operation of a power transformer. Special emphasis was dedicated to recreate the arcing conditions in a tap changer. Arcing inside the tap changer chamber is unavoidable, but excessive arcing leads to a multitude of problems, so that efforts have been made to detect acoustically the signature of the arcing phenomenon. In order to have both flexibility and control over the experimental parameters, the tests were conducted on two sets of test objects, i.e. a model and a small-size tap changer. Focus was made to the type of defects that pose the most imminent threat to the tap changer operation, and the most appropriate methods of signal acquisition and processing were singled out. It is shown that these defects can be recognized based on their specific acoustic signature.
引用
收藏
页码:193 / 197
页数:5
相关论文
共 50 条
  • [21] Hybrid Diagnostic Techniques for High Voltage On-Load Tap Changers
    Riaz, Zain
    Wouters, Peter
    Riaz, Fahim
    van der Wielen, Peter
    Wetzer, Jos
    2020 IEEE 29TH INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE), 2020, : 874 - 879
  • [22] Estimate of the repeatability measurement results obtained by acoustic emission method in the diagnosis of on-load tap changers
    Cichon, Andrzej
    Borucki, Sebastian
    Zmarzly, Dariusz
    PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (11B): : 264 - 267
  • [23] Duty based maintenance for on-load transformer tap changers.
    Redfern, MA
    Handley, WRC
    2001 POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, 2001, : 1824 - 1829
  • [24] A Collective Condition Monitoring Algorithm for On-Load Tap-Changers
    Feizifar, Behnam
    Mueller, Zdenek
    Fandi, Ghaeth
    Usta, Omer
    2019 IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2019 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2019,
  • [25] INVESTIGATION OF THE VOLTAGE STABILITY REGION INVOLVING ON-LOAD TAP CHANGERS
    HONG, YY
    WANG, HY
    ELECTRIC POWER SYSTEMS RESEARCH, 1995, 32 (01) : 45 - 54
  • [26] A Review of Fault Diagnosis Research on On-Load Tap-Changers
    Jin, Liang
    Cai, Yuqi
    2019 THE 2ND INTERNATIONAL SYMPOSIUM ON HYDROGEN ENERGY AND ENERGY TECHNOLOGIES (HEET 2019), 2020, 155
  • [27] A new approach to solid-state on-load tap changers
    Demirci, O
    Torrey, DA
    Degeneff, RC
    Schaeffer, FK
    Frazer, RH
    PROCEEDINGS OF THE AMERICAN POWER CONFERENCE, VOL 58, PTS I AND II, 1996, 58 : 957 - 962
  • [28] A Hybrid Diverter Design for Distribution Level On-load Tap Changers
    Rogers, Daniel J.
    Green, Tim C.
    2010 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION, 2010, : 1493 - 1500
  • [29] Electric arc furnace tap changers -a multifaceted approach to improving the reliability and performance of EAF on-load tap changers
    Birkbeck, Chris
    Schwabe, Carl
    Ryan, Steve
    Iron and Steel Technology, 2010, 7 (12): : 40 - 45
  • [30] Diagnostics of the on-load tape changers by means of acoustic emission
    Cichon, Andrzej
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (11B): : 198 - 201