Identification of Cross-Country Fault of Power Transformer for Fast Unblocking of Differential Protection

被引:17
|
作者
Lin, Xiangning [1 ,2 ]
Weng, Hanli [1 ]
Wang, Bin [2 ]
机构
[1] Huazhong Univ Sci & Technol, Elect Power Secur & High Efficiency Lab, Wuhan 430074, Peoples R China
[2] Three Gorges Univ, Coll Elect Engn & Informat Technol, Yichang 443002, Hubei Province, Peoples R China
基金
中国国家自然科学基金;
关键词
Cross-country fault; current-trsnsformer (CT) saturation; differential protection; percentage restraint characteristic; time difference; INTERNAL FAULTS; INRUSH CURRENT; DISCRIMINATION;
D O I
10.1109/TPWRD.2009.2013663
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Due to the different ratings of the current transformers (CT) located on different sides of power transformer, only the CT of low ratings will saturate when the power transformer experiences a heavy through fault, leading to false differential current. Such type of external fault can be identified from the internal one if the differential protection is equipped with the percentage restraint characteristic together with the method using operation time difference between pickup element and differential protection. However, the differential protection will be wrongly blocked as well if a cross-country fault occurs. According to the investigations in this paper, in the event of an external fault accompanied by the CT saturation, the variation of most samples of the secondary current of the saturated CT is inversely proportional to the variation of the differential current. Comparatively, this law cannot be followed on the occasion of an internal fault. In this case, the locus of the variation of the saturated secondary current with the differential current can be used to dynamically discriminate if an external fault develops to an internal fault. With the method proposed in this paper, the ability of the differential protection immune to cross-country fault can be improved further. The effectiveness of the proposed method is verified with the simulation tests.
引用
收藏
页码:1079 / 1086
页数:8
相关论文
共 50 条
  • [1] A Wavelet-Based Transformer Differential Protection With Differential Current Transformer Saturation and Cross-Country Fault Detection
    Costa, Flavio
    Prado, Rodrigo
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [2] A Wavelet-Based Transformer Differential Protection With Differential Current Transformer Saturation and Cross-Country Fault Detection
    Medeiros, Rodrigo Prado
    Costa, Flavio Bezerra
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) : 789 - 799
  • [3] Performance Improvement of Transformer Differential Protection During Cross-Country Fault Using Hyperbolic S-Transform
    Shahbazi, Nassim
    Bagheri, Sajad
    Gharehpetian, Gevork B.
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2022, 71
  • [4] Protection and Fault Identification in Presence of Power Swing Blocking/Unblocking Function
    Gawande, Prashant
    Dambhare, Sanjay
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [5] Analysis on line protection operation caused by a special cross-country fault
    Chen, Shuiyao
    Qiu, Yutao
    Fang, Yudong
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2008, 32 (15): : 104 - 107
  • [6] Transformer differential protection scheme based on self-adaptive biased characteristic curve and considering cross-country faults
    Shahbazi, Nassim
    Bagheri, Sajad
    Gharehpetian, Gevork B.
    INTERNATIONAL JOURNAL OF CIRCUIT THEORY AND APPLICATIONS, 2023, 51 (03) : 1110 - 1131
  • [7] Power Differential Protection for Transformer Based on Fault Component Network
    Peng, Fang
    Gao, Houlei
    Huang, Jiakai
    Guo, Yifei
    Liu, Yiqing
    Zhang, Yongfeng
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (04) : 2464 - 2477
  • [8] A fast unblocking scheme for distance protection to identify symmetrical fault occurring during power swings
    Lin Xiangning
    Zou Qing
    Lu WenJun
    Wu Kecheng
    Weng Hanli
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 2047 - +
  • [9] Fast power transformer fault classification methods based on protection signals
    Babnik, T
    Gubina, F
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (02) : 205 - 210
  • [10] Cross-country fault protection in Enel Distribuzione's experimental MV Loop Lines
    Codino, A.
    Gatta, F. M.
    Geri, A.
    Lamedica, R.
    Lauria, S.
    Maccioni, M.
    Ruvio, A.
    Calone, R.
    2016 POWER SYSTEMS COMPUTATION CONFERENCE (PSCC), 2016,