A fast unblocking scheme for distance protection to identify symmetrical fault occurring during power swings

被引:0
|
作者
Lin Xiangning [1 ]
Zou Qing [1 ]
Lu WenJun [1 ]
Wu Kecheng [1 ]
Weng Hanli [1 ]
机构
[1] Huazhong Univ Sci & Technol, Coll Elect & Elect Engn, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
distance protection; power swing blocking; change rate of powers; crossing blocking; improved two-instantaneous-value product algorithm;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
It is demonstrated in this paper that the change rate of the sum of three-phase active powers and reactive power are the cosine function and the sinusoidal function with respect to the phase difference between the two power systems during power swings. In this case, they cannot be lower than the threshold of 0.7 after they are normalized. However, they will level off to 0 when a three-phase fault occurs during power swings. Based on this analysis, a cross-blocking scheme to rapidly identify the symmetrical fault occurring during the power swings is therefore proposed. By virtue of the improved two-instantaneous-value-product algorithm, the calculation of the active and reactive power is immune to the variation of the system power frequency. As the integration based criterion, this criterion has high stability. Simulation results show that this scheme is of high reliability and fast time response. The longest time delay is up to 30ms.
引用
收藏
页码:2047 / +
页数:2
相关论文
共 50 条
  • [1] A novel scheme to identify symmetrical faults occurring during power swings
    Lin, Xiangning
    Gao, Yan
    Liu, Pei
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) : 73 - 78
  • [2] Fast Distance Relay Scheme for Detecting Symmetrical Fault During Power Swing
    Pang, Chengzong
    Kezunovic, Mladen
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2205 - 2212
  • [3] A New Blocking Scheme for Distance Protection during Power Swings
    Abidin, Ahmad Farid
    Mohamed, Azah
    Shareef, Hussain
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2010, 11 (01):
  • [4] Rotating negative-sequence phasors for blocking and unblocking the distance protection during power swings
    Paula, Henrique
    Pereira, Clever S.
    De Conti, Alberto
    Morais, Adriano P.
    Silveira, Eduardo G.
    Andrade, Johnny S.
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 202
  • [6] A NEW BLOCKING PRINCIPLE WITH PHASE AND EARTH FAULT-DETECTION DURING FAST POWER SWINGS FOR DISTANCE PROTECTION
    MECHRAOUI, A
    THOMAS, DWP
    IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (03) : 1242 - 1248
  • [7] Fault identification during power swings with symmetrical component
    Yang, QX
    Xu, ZY
    Lai, LL
    Zhang, ZH
    Rajkumar, N
    PROCEEDINGS OF EMPD '98 - 1998 INTERNATIONAL CONFERENCE ON ENERGY MANAGEMENT AND POWER DELIVERY, VOLS 1 AND 2 AND SUPPLEMENT, 1998, : 108 - 111
  • [8] New principle for high resistance earth fault detection during fast power swings for distance protection.
    Mechraoui, A
    Thomas, DWP
    IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) : 1452 - 1457
  • [9] Fault identification during power swings with symmetrical component
    Sifang Protection & Control Ltd, Shangde, China
    Proc Int Conf Energy Manage Power Delivery EMPD, (108-112):
  • [10] A Novel Earth Fault Detection Scheme to Empower Distance Protection during Asymmetrical Power Swings with Inverter based Resources
    Jalilian, Amin
    Muttaqi, Kashem M.
    Sutanto, Danny
    Robinson, Duane
    2021 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING (IAS), 2021,