Performance analysis of a ductless personalized ventilation combined with radiant floor cooling system and displacement ventilation

被引:40
|
作者
Liu, Jiying [1 ,2 ]
Dalgo, Daniel Alejandro [2 ]
Zhu, Shengwei [1 ]
Li, Hui [3 ]
Zhang, Linhua [3 ]
Srebric, Jelena [2 ]
机构
[1] Shandong Jianzhu Univ, Sch Thermal Engn, Jinan 250101, Shandong, Peoples R China
[2] Univ Maryland, Dept Mech Engn, College Pk, MD 20742 USA
[3] Shandong Jianzhu Univ, Minist Educ, Key Lab Renewable Energy Utilizat Technol Bldg, Jinan 250101, Shandong, Peoples R China
基金
中国国家自然科学基金;
关键词
computational fluid dynamics (CFD); ductless personalized ventilation (DPV); displacement ventilation (DV); radiant floor cooling system (RFCS); INDOOR THERMAL COMFORT; AIR-CONDITIONING SYSTEM; ENERGY PERFORMANCE; CFD; CONJUNCTION; ROOMS; TEMPERATURE; EFFICIENCY; QUALITY; SAVINGS;
D O I
10.1007/s12273-019-0521-9
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study conducted the numerical simulation to evaluate the performance of a ductless personalized ventilation (DPV) combined with radiant floor cooling system (RFCS) and displacement ventilation (DV) system. In the non-DPV cases, DV supplies air at temperature of 16 degrees C and 20 degrees C, respectively with a flow rate of 2.4 ACH. In the cases with DPV, DPV supplies personalized air, which is drawn at the height of 0.1 m or 0.2 m above the floor, to the face of a seated occupant at flow rates of 3 L/s, 5 L/s and 7 L/s, respectively. The horizontal distance of 0.3 m is designed between DPV air supply opening and occupant face at the height of 1.2m. For all the cases, the floor cooling temperature is set to 20 degrees C. The vertical air temperature difference at 1.1 m and 0.1 m (Delta T1.1-0.1), the contaminant removal effectiveness (epsilon) and the draft rate at the occupant face (DRface) are mainly used as evaluation indices to quantify the ventilation effectiveness and thermal comfort effect. According to the results, DPV remarkably decreases Delta T1.1-0.1 with a maximum reduction of 1.79 degrees C compared to non-DPV case. DPV significantly influences the temperature adjacent to the face at the breathing zone, with a maximum reduction of 4.44 degrees C from non-DPV case to DPV case. DPV cases also effectively improve epsilon at breathing region compared to the non-DPV case. The DRface ranges from 9.01% to 21.33% when different flow rates of DPV are used. In summary, the case using DPV flow rate of 5 L/s and at intake height of 0.1 m presented relatively better ventilation effectiveness and thermal comfort environment around the occupant.
引用
收藏
页码:905 / 919
页数:15
相关论文
共 50 条
  • [31] Study on Indoor Air Quality of Ceiling Radiant Cooling Panel System Integrated with Displacement Ventilation
    Du, Jing
    Li, Nianping
    PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 1: INDOOR AND OUTDOOR ENVIRONMENT, 2014, 261 : 497 - 505
  • [32] In-Situ Performance of Displacement Ventilation System in Canadian Schools with Radiant Heating Systems
    Ouazia, Boualem
    Tardif, Michel
    Macdonald, Iain
    Thompson, Alexandra
    Booth, Daniel
    ASHRAE TRANSACTIONS 2011, VOL 117, PT 2, 2011, 117 : 207 - 219
  • [33] OPTIMIZED RESEARCH OF RADIANT COOLER AND DISPLACEMENT VENTILATION COMPLEX SYSTEM
    Liu, X. M.
    Zhao, J. Y.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 1033 - 1039
  • [34] An innovative personalized displacement ventilation system for airliner cabins
    You, Ruoyu
    Zhang, Yongzhi
    Zhao, Xingwang
    Lin, Chao-Hsin
    Wei, Daniel
    Liu, Junjie
    Chen, Qingyan
    BUILDING AND ENVIRONMENT, 2018, 137 : 41 - 50
  • [35] Performance evaluation of ductless personalized ventilation in comparison with desk fans using numerical simulations
    Alsaad, Hayder
    Voelker, Conrad
    INDOOR AIR, 2020, 30 (04) : 776 - 789
  • [36] Numerical optimization of a novel ceiling radiant cooling panel combined with wall attached ventilation system
    Ye, Minzhi
    Serageldin, Ahmed A.
    Nagano, Katsunori
    Case Studies in Thermal Engineering, 2021, 26
  • [37] Research and analysis on floor radiant cooling system
    Hu, S
    Zhang, Y
    Zhang, L
    INDOOR AIR 2005: PROCEEDINGS OF THE 10TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY AND CLIMATE, VOLS 1-5, 2005, : 750 - 754
  • [38] Numerical optimization of a novel ceiling radiant cooling panel combined with wall attached ventilation system
    Ye, Minzhi
    Serageldin, Ahmed A.
    Nagano, Katsunori
    CASE STUDIES IN THERMAL ENGINEERING, 2021, 26
  • [39] Floor Heating with Displacement Ventilation: An Experimental and Numerical Analysis
    Causone, Francesco
    Olesen, Bjarne W.
    Corgnati, Stefano P.
    HVAC&R RESEARCH, 2010, 16 (02): : 139 - 160
  • [40] A comparative experimental investigation on radiant floor heating system and stratum ventilation
    Li, Han
    Xi, Chang
    Kong, Xiangfei
    Lin, Zhang
    Wang, Lu
    SUSTAINABLE CITIES AND SOCIETY, 2020, 52