Preliminary study on fire protection of window glass by water mist curtain

被引:12
|
作者
Wang, Xishi [1 ]
Tan, Qiong [1 ,2 ]
Wang, Zhigang [1 ]
Kong, Xiangxiao [1 ]
Cong, Haiyong [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
[2] Operat & Monitoring Ctr Hefei Urban Safety & Secu, Hefei 230601, Anhui, Peoples R China
关键词
Building fire; Water mist curtain; Radiant heat attenuation; Window glass; INDUCED THERMAL FIELDS; HEAT-RESISTANCE; FILM; PANE; TEMPERATURE; ATTENUATION; RADIATION; SPRINKLER; BREAKING;
D O I
10.1016/j.ijthermalsci.2017.11.013
中图分类号
O414.1 [热力学];
学科分类号
摘要
Glass may easily break during a fire that can significantly accelerate the enclosure fire development. Water mist, as an efficient fire suppression technique, has been used for fire protection of an object due to fire radiant heat attenuation. The main purpose of this work is to investigate the behavior of the window glass heated by a fire and protected by a water mist curtain (WMC). Float glass with a dimension of 600 x 600 x 6 mm(3) exposed to a 0.16 MW gas fire was tested. The WMC was generated by a single orifice nozzle with K-factor of 1.01 L/min/ MPa1/2. The initial time of glass breakage, the temperature difference of the glass pane and the heat flux penetrating through the glass were measured and compared. The time of the window glass pane maintaining its integrated structure under the protection of WMC extends to more than 600 s comparing to 150 s of that without the protection of WMC. More than 38.5% thermal radiation of the fire would be attenuated by the WMC with thickness of 0.075 m and operating pressure of 1.0 MPa. The WMC demonstrates a better cooling capacity that can protect the glass from breakage more effectively comparing to water film with same flow rate. It is also found that the delaying of the activation of the WMC system contributes little to the crack or fallout of the float glass. The results may be helpful for providing guidelines on keeping glass integration in building fire scenarios.
引用
收藏
页码:44 / 51
页数:8
相关论文
共 50 条
  • [21] Experimental study of pool fire suppression by water mist in enclosure
    State Key Laboratory of Fluid Power Transmission and Control, Zhejiang University, Hangzhou 310027, China
    不详
    Zhejiang Daxue Xuebao (Gongxue Ban), 2007, 6 (1029-1035):
  • [22] Experimental Study of Spirits Leakage Fire Suppression with Water Mist
    Chen Lueyi
    Cai Xin
    Lu Jia
    Wang Deyong
    Liao Guangxuan
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL VII, PTS A AND B, 2008, 7 : 774 - 778
  • [23] Experimental study on the effectiveness of the extinction of a pool fire with water mist
    Wang, XS
    Liao, GX
    Qin, J
    Fan, WC
    JOURNAL OF FIRE SCIENCES, 2002, 20 (04) : 279 - 295
  • [24] The development of water mist fire protection systems for U.S. Navy ships
    Darwin, R.L.
    Williams, F.W.
    1600, American Society of Naval Engineers (112):
  • [25] Water mist fire suppression systems
    Dyer, J.
    Fire Engineers Journal, 1997, 57 (191):
  • [26] Will water mist improve fire safety?
    Scott, D.
    Pankahnia, N.
    World Tunnelling, 2001, 14 (08): : 384 - 385
  • [27] A high-pressure water mist system - Clean Fire Protection for Gas Turbines
    Voutilainen, Heikki
    Rohrbacher, D. I. Herbert
    Proceedings of the ASME Turbo Expo 2005, Vol 4, 2005, : 285 - 295
  • [28] A novel method to evaluate fire test performance of water mist and water spray total compartment protection
    Arvidson, Magnus
    JOURNAL OF FIRE PROTECTION ENGINEERING, 2013, 23 (04) : 277 - 299
  • [29] Experimental and Numerical Study of Water Mist Fire Suppression System Effectiveness on Shielded Fire
    Kuswantoro
    Nugroho, Y. S.
    3RD INTERNATIONAL TROPICAL RENEWABLE ENERGY CONFERENCE SUSTAINABLE DEVELOPMENT OF TROPICAL RENEWABLE ENERGY (I-TREC 2018), 2018, 67
  • [30] A study of portable water mist fire extinguishers used for extinguishment of multiple fire types
    Liu, Zhigang
    Kim, Andrew K.
    Carpenter, Don
    FIRE SAFETY JOURNAL, 2007, 42 (01) : 25 - 42