Short circuit fault analysis in a grid connected DFIG based wind energy system with active crowbar protection circuit for ridethrough capability and power quality improvement

被引:71
|
作者
Swain, Snehaprava [1 ]
Ray, Pravat Kumar [1 ]
机构
[1] Natl Inst Technol, Dept Elect Engn, Rourkela 769008, India
关键词
Doubly Fed Induction Generator (DFIG); Fault Ride through (FRT); Active crowbar protection; Wind Energy Conversion System (WECS); FED INDUCTION GENERATOR; VOLTAGE-RIDE-THROUGH; STORAGE SYSTEM; CONTROL STRATEGY; TURBINES; ENHANCEMENT; STATCOM; INTEGRATION;
D O I
10.1016/j.ijepes.2016.05.006
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In power industry, improvement of the short circuit Fault-ride through (FRT) capability of grid integrated Doubly Fed Induction Generators (DFIGs) for the wind power system is an important issue. In this paper an Active Crowbar Protection (ACB_P) system is proposed to enhance the Fault-ride through (FRT) capability of DFIG so as to improve the power quality of the system. The protection scheme proposed here is designed with a capacitor in series with the resistor unlike, the conventional Crowbar (CB) having only resistors. The importance of ACB_P is to maintain the connection of DFIG with the grid during fault conditions to provide uninterruptable power supply to the loads. The major functions of the capacitor in the protection circuit are to eliminate the ripples generated in the rotor current and to protect the converters as well as the DC-link capacitor. The main objectives of the proposed approach are: minimisation of magnitude of rotor fault currents, maintenance of constant DC-link voltage, reduction in crowbar operation time to avoid disconnection between the DFIG and the Rotor side converter (RSC), improvement in the short circuit response of terminal voltage and enhancement in the dynamic responses of the DFIG. These objectives are achieved through the incorporation of ACB_P scheme between the rotor of the DFIG and RSC. The proposed scheme is validated on different types of fault conditions and it is observed that there is significant improvement in the objectives. Simulation results are carried out on a 1.7 MVA DFIG based WECS under different types of short circuit faults in MATLAB/Simulation and functionality of the proposed scheme is verified. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:64 / 75
页数:12
相关论文
共 50 条
  • [1] Fault Analysis in a Grid Integrated DFIG Based Wind Energy System with NA CB_P Circuit for Ridethrough Capability and Power Quality Improvement
    Swain, Snehaprava
    Ray, Pravat Kumar
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2016, 17 (06): : 619 - 630
  • [2] Study on LVRT of DFIG Wind Power System Based on Crowbar Protection Circuit
    Wang, Renxiao
    Song, Huihui
    Han, Li
    Yan, Luocheng
    Wang, Bin
    Zhao, Pu
    2018 1ST IEEE STUDENT CONFERENCE ON ELECTRIC MACHINES AND SYSTEMS (IEEE SCEMS), 2018,
  • [3] Short circuit current analysis for DFIG-based wind generation system with Crowbar protection under grid faults
    Zheng, Zhong
    Yang, Geng
    Geng, Hua
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2012, 32 (11): : 7 - 15
  • [4] Short Circuit Current Analysis of DFIG Wind Turbines with Crowbar Protection
    Zhou, H. L.
    Yang, G.
    Li, D. Y.
    2009 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1-3, 2009, : 1731 - 1736
  • [5] Fault Ridethrough and Power Quality Improvement of Doubly-Fed Induction Generator based Wind Turbine System during Grid Fault with Novel Active Crowbar Protection Design
    Swain, Snehaprava
    Ray, Pravat Kumar
    PROCEEDINGS OF THE 2016 IEEE REGION 10 CONFERENCE (TENCON), 2016, : 2628 - 2633
  • [6] Short Circuit Current Analysis of DFIG-type WG with Crowbar Protection under Grid Faults
    Zheng, Zhong
    Yang, Geng
    Geng, Hua
    2012 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE), 2012, : 1072 - 1079
  • [7] Investigation of Transient Torque during a Power System Fault in Wind Power Turbines Having a DFIG and Crowbar Circuit
    Cheng, Mengzeng
    Cai, Xu
    Wu, Guoxiang
    PRZEGLAD ELEKTROTECHNICZNY, 2011, 87 (11): : 245 - 250
  • [8] Reactive Power Generation and Optimization during a Power System Fault in Wind Power Turbines having a DFIG and Crowbar Circuit
    Cheng, Mengzeng
    Cai, Xu
    WIND ENGINEERING, 2011, 35 (02) : 145 - 163
  • [9] Voltage recovery of grid-connected wind turbines with DFIG after a short-circuit fault
    Sun, T
    Chen, Z
    Blaabjerg, F
    PESC 04: 2004 IEEE 35TH ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, CONFERENCE PROCEEDINGS, 2004, : 1991 - 1997
  • [10] Response and protection of DFIG system under three-phase short circuit fault of grid
    Guo, Jia-Hu
    Zhang, Lu-Hua
    Cai, Xu
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (06): : 40 - 44