Fault Analysis in a Grid Integrated DFIG Based Wind Energy System with NA CB_P Circuit for Ridethrough Capability and Power Quality Improvement

被引:1
|
作者
Swain, Snehaprava [1 ]
Ray, Pravat Kumar [1 ]
机构
[1] Natl Inst Technol, Dept Elect Engn, Rourkela 769008, India
关键词
doubly fed induction generator (DFIG); fault ride through (FRT); novel active crowbar protection; wind energy conversion system (WECS);
D O I
10.1515/ijeeps-2016-0095
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper a three phase fault analysis is done on a DFIG based grid integrated wind energy system. A Novel Active Crowbar Protection (NACB_P) system is proposed to enhance the Fault-ride through (FRT) capability of DFIG both for symmetrical as well as unsymmetrical grid faults. Hence improves the power quality of the system. The protection scheme proposed here is designed with a capacitor in series with the resistor unlike the conventional Crowbar (CB) having only resistors. The major function of the capacitor in the protection circuit is to eliminate the ripples generated in the rotor current and to protect the converter as well as the DC-link capacitor. It also compensates reactive power required by the DFIG during fault. Due to these advantages the proposed scheme enhances the FRT capability of the DFIG and also improves the power quality of the whole system. Experimentally the fault analysis is done on a 3hp slip ring induction generator and simulation results are carried out on a 1.7 MVA DFIG based WECS under different types of grid faults in MATLAB/Simulation and functionality of the proposed scheme is verified.