Experimental study on the effect of condensate water on the performance of split air conditioning system

被引:23
|
作者
Yang, Hua [1 ,3 ]
Pei, Na [1 ,2 ]
Liu, Liansheng [1 ,3 ]
Fan, Man [1 ,3 ]
Qin, Yue [1 ]
机构
[1] Hebei Univ Technol, Sch Energy & Environm Engn, Tianjin 300401, Peoples R China
[2] North China Univ Sci & Technol, Qinggong Coll, Tangshan 063000, Peoples R China
[3] Hebei Key Lab Thermal Sci & Energy Clean Utilizat, Tianjin, Peoples R China
关键词
Split air conditioner; Condensate water; Unit performance; Energy efficiency ratio; IMPROVED ENERGY PERFORMANCE; COOLED CHILLER; ENHANCEMENT; HOT;
D O I
10.1016/j.egyr.2021.01.037
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A method of using condensate water to reduce the airflow temperature around the air conditioner condenser and improve the performance of air conditioner is presented in this study. The structure of traditional split air conditioner is adjusted by changing the installation direction of fan and adding disk-type atomization cooling element (ACE) in the outdoor unit. The performance of the air conditioner under four modes is tested in different environment temperatures. Four modes were named, i.e. the original unit without ACE, original unit with ACE, blowing mode without condensate water and blowing mode with condensate water. The blowing mode with condensate water is used to pre-cool the incoming airflow, and the maximum temperature reduction at the air outlet surface of the condenser is up to 2.2 degrees C in 35 degrees C. With the environment temperature increasing, the refrigerating capacity of four modes decreased, and the power consumption increased, leading to the decrease of EER. However, owing to the cooling effect of condensate water, the performance of blowing mode with condensate water was greatly improved compared with the original unit without ACE. The variation rates of refrigerating capacity, power consumption and EER at environment temperature of 43 degrees C were 8.1%,-9.5% and 20%, respectively. The unit with condensate water could greatly improve the performance of air conditioning in high environment temperatures. (C) 2021 The Author(s). Published by Elsevier Ltd.
引用
收藏
页码:840 / 851
页数:12
相关论文
共 50 条
  • [1] Enhancement of condensate water quantity and coefficient of performance of an air conditioning system: An experimental study
    Meher, Raghavarapu Satya
    Jaikumar, Sagari
    HEAT TRANSFER, 2021, 50 (05) : 4144 - 4151
  • [2] Experimental investigation on the performance of residential air conditioning system using water condensate for subcooling
    Sumeru, Kasni
    Pramudantoro, Triaji Pangripto
    Setyawan, Andriyanto
    3RD ANNUAL APPLIED SCIENCE AND ENGINEERING CONFERENCE (AASEC 2018), 2018, 197
  • [3] An experimental study on the performance of air/water direct contact air conditioning system
    Yoo, SY
    Kwon, HK
    KSME INTERNATIONAL JOURNAL, 2004, 18 (06): : 1002 - 1009
  • [4] An experimental study on the performance of air/water direct contact air conditioning system
    Seong-Yeon Yoo
    Hwa-Kil Kwon
    KSME International Journal, 2004, 18 : 1002 - 1009
  • [5] The Effect of Condensate Water on the Performance of Automotive Air Conditioning System under Difference Evaporator Air Inlet Temperature
    Sukri, Mohamad Firdaus
    Lokman, Rusmiati
    Muhajir, Asjufri
    Wasbari, Faizil
    Damanhuri, Amir Abdullah Muhamad
    Sumeru, Kasni
    INTERNATIONAL JOURNAL OF NANOELECTRONICS AND MATERIALS, 2020, 13 : 85 - 93
  • [6] An experimental study on air conditioning water heater system
    Liu, Fei
    Zhuang, Rong
    Chen, Bo
    PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 467 - +
  • [7] Experimental research of performance on air conditioning system with water film
    Zhu, Xingwang
    Nie, Xueli
    Lv, Yanli
    Zhimin, Guo
    Su, Yugui
    Energy Education Science and Technology Part A: Energy Science and Research, 2012, 30 (SPEC .ISS.1): : 1195 - 1200
  • [8] Experimental Study on Energy Performance of a Split-type Air Conditioning System by Cooling Panel Coupled
    Kietkangsadan, S.
    Jiamrittiwong, P.
    Puangngernmak, N.
    Mangkonkaeo, A.
    2021 INTERNATIONAL CONFERENCE ON SMART CITY AND GREEN ENERGY (ICSCGE 2021), 2021, : 18 - 21
  • [9] Effect of Compressor Discharge Cooling Using Condensate on Performance of Residential Air Conditioning System
    Sumeru, K.
    Sunardi, Cecep
    Sukri, M. F.
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON THERMOFLUIDS 2017 (THERMOFLUID 2017), 2018, 2001
  • [10] The application of condensate water as an additional cooling media intermittently in condenser of a split air conditioning
    Ardita, I. N.
    Subagia, I. W. A.
    2ND INTERNATIONAL JOINT CONFERENCE ON SCIENCE AND TECHNOLOGY (IJCST) 2017, 2018, 953