Reliability equivalents for AC adequacy evaluation of large power systems

被引:1
|
作者
Maghraby, HM [1 ]
Farag, AS [1 ]
Cheema, AN [1 ]
机构
[1] King Fahd Univ Petr & Minerals, Dhahran 31261, Saudi Arabia
来源
ELECTRIC MACHINES AND POWER SYSTEMS | 1998年 / 26卷 / 05期
关键词
D O I
10.1080/07313569808955838
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The concept of utilizing the equivalent in the reliability evaluation of large power systems, where sensitivity analysis is to be done or the impact of the further interconnected system is to be examined, is a very powerful and useful tool. In this paper, an adequacy equivalent model of a predefined area of a power system has been developed, utilizing the a.c. power flow method. Two types of equivalencing models, namely, Deterministic and Probabilistic models, are formulated and can be utilized to assess the adequacy of a small area in a composite power system. The equivalent models present the variation of transmission equipment in external areas, utilizing the concept of distribution factors. The validation of the equivalent model is accomplished by comparing results of load flow analysis of the original and equivalent systems. Mismatches may appear for some cases at boundary buses which may be reduced by introducing buffer zones between areas of interest and boundary buses. The execution time required for the adequacy analysis of composite power system is reduced significantly, as the number of states is reduced significantly with respect to the original system.
引用
收藏
页码:507 / 527
页数:21
相关论文
共 50 条