Protection Coordination Method Using Symmetrical Components in Loop Distribution System

被引:2
|
作者
Lee, Jung-Hun [1 ]
Kim, Woo-Hyun [1 ]
Lee, Hak-Ju [1 ]
Kim, Jun-Oh [2 ]
Chae, Woo-Kyu [1 ]
机构
[1] KEPCO Res Inst, Smart Power Distribut Lab, Distribut Planning Grp, Daejeon 34056, South Korea
[2] Korea Elect Power Corp, Daegu 41590, South Korea
关键词
protection coordination; loop distribution system; symmetric component; distributed generations; STRATEGY;
D O I
10.3390/en14164947
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Power utilities worldwide commonly use the radial distribution system because of its advantages of being simple in structure and having relatively inexpensive installation costs. It has a disadvantage in that its power supply reliability is low because the load side of the fault section will suffer from an outage in the event of a fault in the system. However, recently, with ICT (Information and Communication Technologies) development, system reliability is required to be high as the outage-susceptible loads increase. In addition, the increase in the connection of distributed resources such as renewable energy and electric vehicles is making it impossible to predict the power flow and reducing line utilization. Therefore, a loop power distribution system is proposed as a measure to solve this problem. Because all buses (nodes) in a loop distribution system have two or more power supply routes, they are more reliable than the radial system. It allows them to improve line utilization by connecting lines with different load peak times. However, in the case of a fault in the loop distribution system, the fault current is supplied from both directions, making it impossible to properly isolate the fault section with the protection method of the conventional distribution system. The permissive overreach transfer trip (POTT) method using communication to compensate for the limitations of conventional protection devices, and the other method using directional distance relay, is proposed. However, these methods operate by determining the direction of the fault current but have a disadvantage. It is difficult to detect a fault due to the effects of ground faults and distributed generation (DG) occurring in other lines. Therefore, in this paper, we propose a protection coordination algorithm that uses the negative-sequence component of voltage and current that occur when an unbalanced fault occurs, rather than the determination of the directionality and use of communication. To validate this, we configured a system using PSCAD/EMTDC (Manitoba Hydro International Ltd., Winnipeg, Manitoba, Canada), a system analysis program package and verified the results depending on the type of faults with the proposed algorithm.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] A fast method for identification of symmetrical components for power system protection
    El-Naggar, KM
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2001, 23 (08) : 813 - 817
  • [2] Protection coordination analysis of closed-loop distribution system
    Shen, KY
    Gu, JC
    [J]. POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 702 - 706
  • [3] Improved overcurrent protection using symmetrical components
    Lotfi-fard, Saeed
    Faiz, Jawad
    Iravani, Reza
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) : 843 - 850
  • [4] Improved protection systems using symmetrical components
    Kojovic, LA
    Witte, JF
    [J]. 2001 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION, VOLS 1 AND 2: DEVELOPING NEW PERSPECTIVES, 2001, : 47 - 52
  • [6] Digital measurement of symmetrical components for power system protection
    Soliman, SA
    Mahdi, AM
    AlKandari, AM
    ElArini, MM
    [J]. ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 1995, 20 (4A): : 649 - 660
  • [7] A feeder protection method against the phase-phase fault using symmetrical components
    Ciontea, Catalin Iosif
    Bak, Claus Leth
    Blaabjerg, Frede
    Ciontea, Catalin Iosif
    Madsen, Kjeld Kilsgaard
    Sterregaard, Claes Holl
    [J]. 2017 IEEE ELECTRIC SHIP TECHNOLOGIES SYMPOSIUM (ESTS), 2017, : 56 - 63
  • [8] DIGITAL LINE DIFFERENTIAL PROTECTION USING SYMMETRICAL COMPONENTS
    LOBOS, T
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1991, 22 (02) : 85 - 89
  • [9] Protection of power semiconductors in inverters, using fuses and their coordination with the protection schemes of the distribution system
    Gómez, J.C.
    Vaschetti, J.
    Piumetto, M.
    Arcurio, J.
    Coyos, C.
    [J]. Renewable Energy and Power Quality Journal, 2021, 19 : 483 - 486
  • [10] A Study on the Protection Coordination of Korean Distribution System using IEC Curve
    Kim, J. S.
    Cho, G. J.
    Song, J. S.
    Kim, C. H.
    Cho, N. H.
    [J]. 2019 IEEE PES GTD GRAND INTERNATIONAL CONFERENCE AND EXPOSITION ASIA (GTD ASIA), 2019, : 460 - 465