Spray characteristics determination of water mist for suppressing pool fire

被引:0
|
作者
Zheng, Li G. [1 ,2 ]
Yu, Ming G. [1 ]
Yu, Shui J. [1 ]
Liu, Zhi C. [1 ]
机构
[1] Henan Polytech Univ, Sch Safety Sci & Engn, Jiaozuo 454003, Henan, Peoples R China
[2] Zhejiang Univ, Inst Thermal Power Engn, Hangzhou 310027, Peoples R China
关键词
water mist; fire suppression; two-phase flow; measurement;
D O I
暂无
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
To optimize the design of a water mist fire suppression system or to provide input data and validation data for field models, the characteristics of the water mist field are needed. This data typically consists of the distribution of droplet sizes and velocities. In this research a LS2000 Laser Sizer has been proposed to simultaneously determine spray characteristics of 408 kinds of self-developed nozzles for fire suppression. The results of LS2000 Laser Sizer measurements to characterize the water mist produced by nozzles for suppressing pool fire are presented. These data can provide a foundation to the design and optimization of additive-containing WMFSS. To explore the effect of the water pressure on the droplet size distribution and spray velocity, data from three typical pressures of 0.9MPa, 1.2Mpa and I.5MPa have been obtained. With the measured average size and distribution of droplets, a comparison between three nozzles was made in the pressure of 1.5MPa to investigate the influence of the nozzle design parameters on atomizing characteristics. The results show that representative size of droplets decreases slightly and the water flow rate increases with the water pressure to the nozzle head P., and the droplet velocity of water mist is approximately directly proportional to P.. The trends that the nozzles with the larger D-32 have a wider range of droplet diameter distribution and their volume fraction curves shift towards the large diameter direction are also found in measurements. This will be favorable to the extinguishment of kerosene pool fire. The water flux density distribution results demonstrated that the water flux density over the cross section was very non-uniform when the water mist nozzle is improperly designed.
引用
收藏
页码:530 / +
页数:3
相关论文
共 50 条
  • [21] Experimental study on suppressing PVC fire with water mist in a confined space
    Liu, Jianghong
    Qin, Jun
    Huang, Xin
    Liao, Guangxuan
    POLYMER DEGRADATION AND STABILITY, 2007, 92 (05) : 747 - 751
  • [22] Thermal Environments Induced by a Pool Fire with and without Discharging Water Mist
    Gao, Y.
    Liu, P.
    Li, S. S.
    Chow, W. K.
    ARCHITECTURAL SCIENCE REVIEW, 2009, 52 (03) : 176 - 182
  • [23] Experimental investigation of suppression effectiveness on oil pool fire by water mist
    Yu Minggao
    Zuo Qiuling
    Zheng Ligang
    Jia Hailin
    Xu Jun
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL 6, PTS A AND B, 2006, 6 : 1031 - 1034
  • [24] Experiments on pool fire extinguishment with water mist produced by effervescent atomizer
    Huang, X
    Liu, JH
    Liao, GX
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL V, PTS A AND B, 2005, 5 : 1170 - 1175
  • [25] Experimental and numerical study of pool fire suppression using water mist
    Jenft, A.
    Collin, A.
    Boulet, P.
    Pianet, G.
    Breton, A.
    Muller, A.
    FIRE SAFETY JOURNAL, 2014, 67 : 1 - 12
  • [26] Experimental study on extinguishing pool fire sheltered by barrier with water mist
    Jianghong, Liu
    Yudong, Fang
    Guangxuan, Liao
    Lin, Lin
    Journal of Applied Fire Science, 2003, 12 (03): : 209 - 222
  • [27] Water mist (fine spray) fire protection in light hazard occupancies
    Bill Jr., Robert G.
    Ferron, Richard
    Braga, Antonio
    Journal of Fire Protection Engineering, 2000, 10 (03) : 1 - 22
  • [28] Experimental study of suppressing PVC fire with water mist using a cone calorimeter
    Zhang, Yongfeng
    Zhu, Wei
    Zhou, Xiaomeng
    Qin, Jun
    Liao, Guanxuan
    JOURNAL OF FIRE SCIENCES, 2007, 25 (01) : 45 - 63
  • [29] EXPERIMENTAL CLEAN ETHANOL POOL FIRE SUPPRESSION BY USING WARM WATER MIST
    Popa, Constantin
    Chisacof, Alexandru
    Panaitescu, Valeru
    REVUE ROUMAINE DES SCIENCES TECHNIQUES-SERIE ELECTROTECHNIQUE ET ENERGETIQUE, 2012, 57 (03): : 321 - 330
  • [30] A study of the probability distribution of pool fire extinguishing times using water mist
    Liang, Tianshui
    Liu, Mengjie
    Liu, Zhonglin
    Zhong, Wei
    Xiao, Xiukun
    Lo, Siuming
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2015, 93 : 240 - 248