Experimental investigation on thermal management for small container data center

被引:26
|
作者
Chu, Wen-Xiao [1 ]
Hsu, Chang-Sheng [1 ]
Tsui, Yeng-Yung [1 ]
Wang, Chi-Chuan [1 ]
机构
[1] Natl Chiao Tung Univ, Dept Mech Engn, 1001 Univ Rd, Hsinchu 300, Taiwan
关键词
Container data center; Cooling performance; Recirculation; Rack cooling index; Supplied heat index; AISLE CONTAINMENT; AIR; PERFORMANCE;
D O I
10.1016/j.jobe.2018.10.031
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The energy consumptions of data centers are increasing dramatically and cooling systems using for controlling the operating temperature usually consume more than half of these energy. Thus, effective strategies on thermal management in data centers may have benefit on energy savings. In order to improve the power usage effectiveness (PUE) of data centers, the effects of air supply flowrate by computer room air handler (CRAH), intake flowrate of rack cooling fans, air supply grilles and heat load distribution on the cooling performance of a typical small container data center having overhead air supply system are investigated in this paper. The rack cooling index (RCI) and supply heat index (SHI) are incorporated to evaluate the local and average cooling performance of data racks. It is found that the intake flowrate of rack cooling fans plays dominant role, which is suggested to be greater than the air supply flowrate in normal operation. Meanwhile, the volumetric flowrate distribution of grilles is studied. The additional front grille before entering the cold aisle may improve the RCI and SHI of front rack (rack A), in which severe hot-air recirculation may occur in typical operation. Conversely, additional rear grille at the exit of cold aisle has negative effect on cooling performance of the last rack (rack E). Based on the measurement of local temperature distribution, the non-uniform heat load distribution in racks is proposed. Result shows that the RCI can be improved to 64% if more power is placed at lower half part, which is eligible for energy saving. However, the non-uniform heat load distribution shows limited improvement on the rear rack (rack E).
引用
收藏
页码:317 / 327
页数:11
相关论文
共 50 条
  • [1] CFD Investigation of Airflow Management in a Small Container Data Center
    Chu, Wenxiao
    Wang, Chi-Chuan
    IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2019, 9 (11): : 2177 - 2188
  • [2] Experimental Investigation Regarding Rack Pressure Resistance on Cooling Performance of a Container Data Center
    Chu, Wen-Xiao
    Wang, Rui
    Wang, Chi-Chuan
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2019, 27 (04)
  • [3] Numerical simulation on a thermal management system for a small data center
    Zhou, Chenglong
    Yang, Chunxin
    Wang, Chao
    Zhang, Xingjuan
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 124 : 677 - 692
  • [4] Challenges of data center thermal management
    Schmidt, RR
    Cruz, EE
    Iyengar, MK
    IBM JOURNAL OF RESEARCH AND DEVELOPMENT, 2005, 49 (4-5) : 709 - 723
  • [5] Challenges of data center thermal management
    Schmidt, R.R. (c28rrs@us.ibm.com), 1600, IBM Corporation (49): : 4 - 5
  • [6] Advances in data center thermal management
    Fulpagare, Yogesh
    Bhargav, Atul
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 43 : 981 - 996
  • [7] A Modified Approach for Thermal Distribution Monitoring of the Container Data Center by Thermal Image Registration
    Liu, Hang
    Xie, Ting
    Ran, Jian
    Gao, Shan
    2016 9TH INTERNATIONAL CONGRESS ON IMAGE AND SIGNAL PROCESSING, BIOMEDICAL ENGINEERING AND INFORMATICS (CISP-BMEI 2016), 2016, : 259 - 263
  • [8] THERMAL PROFILING OF A SMALL OPERATIONAL DATA CENTER
    Turkmen, Ismail
    Mercan, Cem Ahmet
    Erden, Hamza Salih
    PROCEEDINGS OF THE ASME INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, 2019, 2020,
  • [9] Numerical and experimental investigations on thermal management for data center with cold aisle containment configuration
    Lee, Yee-Ting
    Wen, Chih-Yung
    Shih, Yang-Cheng
    Li, Zhengtong
    Yang, An-Shik
    APPLIED ENERGY, 2022, 307
  • [10] Impact of Overhead Air Supply Layout on the Thermal Performance of a Container Data Center
    Chu, Wen-Xiao
    Wu, Jui-Lin
    Tsui, Yeng-Yung
    Wang, Chi-Chuan
    JOURNAL OF ELECTRONIC PACKAGING, 2020, 142 (01)