Line loss minimum control of loop distribution systems using UPFC

被引:0
|
作者
Sayed, Mahmoud A. [1 ]
Inayoshi, Nobuyuki [1 ]
Takeshita, Takaharu [1 ]
Ueda, Fukashi [2 ]
机构
[1] Nagoya Inst Technol, Nagoya, Aichi, Japan
[2] Chubu Electr Power Co Inc, Nagoya, Aichi, Japan
关键词
loop distribution system; line loss minimum; FACTS; unified power flow controller (UPFC);
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an elaborated mathematical analysis of the line loss minimum condition of loop distribution systems. In order to achieve this condition, the unified power How controller (UPFC), a typical FACTS (flexible AC transmission systems) device that is capable of instantaneous control of transmission and distribution power flow, is used. Also, the available control schemes of the UPFC to minimize the total line loss of the loop distribution system are presented. The authors propose the Line Inductance Compensation control and the Line Voltage Compensation control which can be applied to the loop distribution system according to the line parameters. The effectiveness of the proposed control scheme, Line Inductance Compensation control, has been verified experimentally using laboratory prototype in a 200V, 6 kVA system.
引用
收藏
页码:962 / +
页数:2
相关论文
共 50 条
  • [21] Control and performance of UPFC connected to a transmission line
    Kalyani, S. Tara
    Das, G. Tulasiram
    2007 CONFERENCE PROCEEDINGS IPEC, VOLS 1-3, 2007, : 302 - 307
  • [22] Minimum singular value based identification of UPFC control parameters
    Pandey, R. K.
    Singh, N. K.
    TENCON 2006 - 2006 IEEE REGION 10 CONFERENCE, VOLS 1-4, 2006, : 2072 - +
  • [23] Installation of a Sen Transformer in a Loop Distribution System for Line Loss Minimization by Loop Current Elimination
    Patel, Dhrupa
    Chowdhury, Anandita
    ELECTRICA, 2021, 21 (01): : 85 - 95
  • [24] Line Loss Minimization Control in a Loop Distribution System Using Circulating Current Compensation and Reactive Current Suppression by a Unified Power Flow Controller
    Yamada, Kazuhei
    Takeshita, Takaharu
    Kunii, Yasuyuki
    Ueda, Fukashi
    ELECTRICAL ENGINEERING IN JAPAN, 2014, 189 (03) : 30 - 40
  • [25] Double closed loop control and analysis for shunt inverter of UPFC
    Zhang Yong-gao
    Liu Li-ming
    Zhu Peng-cheng
    Liu Xiao-yuan
    Kang Yong
    2005/2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2006, : 666 - +
  • [26] Line Loss Minimization in Radial Distribution Systems using Multiple STATCOMs and Static Capacitors
    Miyazaki, Kensuke
    Takeshita, Takaharu
    IEEJ JOURNAL OF INDUSTRY APPLICATIONS, 2015, 4 (05) : 667 - 673
  • [27] Double closed loop control and analysis for shunt inverter of UPFC
    Zhang, YG
    Liu, LM
    Zhu, PC
    Liu, XY
    Kang, Y
    Gao, YL
    ICEMS 2005: PROCEEDINGS OF THE EIGHTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1-3, 2005, : 1118 - 1123
  • [28] Minimum Heat Loss Control of Fluid-Powered Systems
    Kang, Jiyeon
    Park, Frank C.
    2011 11TH INTERNATIONAL CONFERENCE ON CONTROL, AUTOMATION AND SYSTEMS (ICCAS), 2011, : 1383 - 1387
  • [29] Minimum loss optimization in distribution systems: Discrete ascent optimal programming
    Broadwater, RP
    Dolloff, PA
    Herdman, TL
    Karamikhova, R
    Sargent, AF
    ELECTRIC POWER SYSTEMS RESEARCH, 1996, 36 (02) : 113 - 121
  • [30] Ant colony search - based loss minimum for reconfiguration of distribution systems
    Khoa, T. Q. D.
    Phan, B. T. T.
    2006 IEEE POWER INDIA CONFERENCE, VOLS 1 AND 2, 2006, : 523 - +