Line Loss Minimization Control in a Loop Distribution System Using Circulating Current Compensation and Reactive Current Suppression by a Unified Power Flow Controller

被引:2
|
作者
Yamada, Kazuhei [1 ]
Takeshita, Takaharu [1 ]
Kunii, Yasuyuki [2 ]
Ueda, Fukashi [2 ]
机构
[1] Nagoya Inst Technol Gokiso, Nagoya, Aichi, Japan
[2] Chubu Elect Power Co Inc, Nagoya, Aichi, Japan
关键词
unified power flow controller; line loss minimization; loop distribution system; reactive current suppression; circulating current compensation;
D O I
10.1002/eej.22552
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes line loss minimization control using the shunt and series converters of a UPFC (unified power flow controller) in a loop distribution system. The line losses in a loop distribution system are caused by the circulating current flowing in the loop and the mesh currents flowing to the loads. The authors have previously proposed a compensation method for circulating current using a series converter. In this paper, the authors propose a suppression method for reactive currents using a shunt converter. In the prototype model of a loop distribution system, a theoretical loss reduction ratio of 92% without line loss caused by active currents is obtained. Similar line loss reduction characteristics are obtained in experiments using the prototype distribution system.