Retrofitting of an air-cooled data center for energy efficiency

被引:20
|
作者
Kuzay, Mustafa [1 ,4 ]
Dogan, Aras [1 ,4 ]
Yilmaz, Sibel [1 ]
Herkiloglu, Oguzhan [2 ]
Atalay, Ali Serdar [2 ]
Cemberci, Atilla [2 ]
Yilmaz, Cagatay [3 ]
Demirel, Ender [1 ,4 ]
机构
[1] Design & Simulat Tech Inc, TR-26480 Eskisehir, Turkey
[2] Radius Solut Ctr, Bahar Arkasi St 11, TR-34692 Istanbul, Turkey
[3] Lande Ind Met Prod Inc Co, Organized Ind Zone, 20th St 14, Eskisehir, Turkey
[4] Eskisehir Osmangazi Univ, TR-26480 Eskisehir, Turkey
关键词
Data center; Thermal efficiency; Cooling efficiency; CFD modeling; Open-source; MANAGEMENT;
D O I
10.1016/j.csite.2022.102228
中图分类号
O414.1 [热力学];
学科分类号
摘要
Small-scale data centers suffering from low cooling efficiency consume an intense power for reliable operation of IT equipment. In this study, thermal distribution in an air-cooled data center is simulated using an open source Computational Fluid Dynamics (CFD) model to examine the underlying mechanism that reduces thermal and cooling efficiencies. The numerical model is validated with the temperature measurements conducted in the data center. Numerical simulations have revealed that recirculating hot flows observed at the top of the racks increased the air temperature beyond the allowable maximum temperature. To this end, the data center has been retrofitted by creating a hot aisle with the implementation of a moving baffle at the rear of the rack. Numerical simulations conducted for two working scenarios have demonstrated that such a minor modification could result in remarkable enhancement in the cooling efficiency. Efficiency of the data center has improved by 47.2% and 22.7% with respect to the RCI (Rack Cooling Index) and RHI (Return Heat Index), respectively. The present numerical model can capture distributions of the efficiency metrics over the racks. Present methodology can be used to reduce power consumption by the cooling and ventilation systems in existing data centers.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Improving the energy efficiency of air-cooled heat exchangers
    Kuntysh, VB
    Bessonnyi, AN
    Brill, AA
    CHEMICAL AND PETROLEUM ENGINEERING, 1997, 33 (04) : 402 - 407
  • [2] Improving the energy efficiency of air-cooled heat exchangers
    V. B. Kuntysh
    A. N. Bessonnyi
    A. A. Brill'
    Chemical and Petroleum Engineering, 1997, 33 : 402 - 407
  • [4] ENERGY MODELING OF AIR-COOLED DATA CENTERS: PART II THE EFFECT OF RECIRCULATION ON THE ENERGY OPTIMIZATION OF OPEN-AISLE, AIR-COOLED DATA CENTERS
    Demetriou, Dustin W.
    Khalifa, H. Ezzat
    PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2, 2012, : 395 - 404
  • [5] On energy efficient flow provisioning in air-cooled data servers
    Lucchese, Riccardo
    Johansson, Andreas
    CONTROL ENGINEERING PRACTICE, 2019, 89 : 103 - 112
  • [6] An analysis on the energy efficiency of air-cooled chillers with water mist system
    Yang, Jia
    Chan, K. T.
    Wu, Xiangsheng
    Yu, F. W.
    Yang, Xiaofeng
    ENERGY AND BUILDINGS, 2012, 55 : 273 - 284
  • [8] Impact of a Rotary Regenerative Heat Exchanger on Energy Efficiency of an Air Cooled Data Center
    Mok, Seungho
    Kumar, Satish
    Hutchins, Ronald R.
    Joshi, Yogendra K.
    2016 15TH IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM), 2016, : 1182 - 1190
  • [9] ASHRAE's Data Center Thermal Guidelines- Air-Cooled Evolution
    Quirk, David
    Davidson, Tom
    Schmidt, Roger
    ASHRAE Journal, 2022, 64 (05) : 54 - 60
  • [10] ASHRAE's Data Center Thermal Guidelines- Air-Cooled Evolution
    Quirk, David
    Davidson, Tom
    Schmidt, Roger
    ASHRAE JOURNAL, 2022, 64 : 54 - 58