Correction of Logarithmic Mean Temperature Difference in a compact brazed plate evaporator assuming heat flux governed flow boiling heat transfer coefficient

被引:20
|
作者
Claesson, J [1 ]
机构
[1] Royal Inst Technol, Dept Energy Technol, Div Appl Thermodynam & Refrigerat, SE-10044 Stockholm, Sweden
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2005年 / 28卷 / 04期
关键词
plate exchanger; evaporator; calculation; temperature difference; heat flux; heat transfer coefficient; boiling;
D O I
10.1016/j.ijrefrig.2004.09.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
The heat transfer in heat exchangers is commonly calculated using the concept of Logarithmic Mean Temperature Difference (LMTD). As is well known this approach is only valid for counter-current and co-current heat exchanger configurations. For other configurations, corrections for the deviation from pure counter-current are introduced. From any standard text book in heat transfer it may be found that the LMTD approach may also be used if condensation and evaporation occurs in the heat exchanger. The purpose of the present paper is to investigate if the LMTD approach can be used in a compact brazed plate evaporator. It will be shown through integration of the governing equations that the LMTD approach indeed may be used for practical cases, even though deviations occur at small logarithmic mean temperature differences. The article presents suggestions on the correction factor (F) needed under some simplified assumptions in a compact brazed plate heat exchanger operating as an evaporator for heat pump and refrigeration applications. (c) 2004 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:573 / 578
页数:6
相关论文
共 50 条