Effect of UV system modifications on disinfection performance

被引:25
|
作者
Chiu, KP
Lyn, DA
Savoye, P
Blatchley, ER
机构
[1] Trojan Technol Inc, London, ON N5V 4T7, Canada
[2] Purdue Univ, Sch Civil Engn, W Lafayette, IN 47907 USA
[3] Ctr Int Rech Eau & Environm, Le Pecq, France
来源
关键词
D O I
10.1061/(ASCE)0733-9372(1999)125:5(459)
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Numerical simulations have been performed to gain a better understanding of ultraviolet (UV) disinfection process performance. Similar simulations in previous studies revealed critical paths through which particles moved and experienced low UV doses. In vertical UV systems, these paths generally are found near the channel walls with characteristics of high velocity and low turbulence intensity. Moreover, these paths generally coincide with low UV intensity zones and appear to represent the primary limitation of process performance. Reactor modifications have been designed to eliminate or modify these trajectories, thereby improving process performance. In a pilot-scale open-channel system with a vertical lamp orientation, two geometric modifications with "wave" and "baffle" shapes have been developed and examined. The results of these pilot tests confirmed the improvement of process performance when compared with an unmodified UV system. As in the case of the unmodified UV systems, a numerical model that combines kinetic information from a well-mixed batch reactor with a dose-distribution function was used to predict process performance of the UV system with the wave-shaped modification. A dose-distribution function that incorporates the effects of spatial nonuniformities in both hydrodynamics (through a random-walk model) and UV intensity (through a point-source-summation model) was developed. The dose-response function for microorganisms was obtained from completely mixed batch reactor experiments with a collimated beam. Predictions of disinfection efficacy confirmed the ability of the modified systems to improve microbial inactivation.
引用
收藏
页码:459 / 469
页数:11
相关论文
共 50 条
  • [41] NOVEL UV LIGHT SYSTEM FOR DISINFECTION OF PERITONEAL DIALYSIS CATHETER CONNECTIONS
    Banaei, Niaz
    Calayan, Czarina
    Lance, Justin
    Rasooly, Julia
    Kermode, Jim
    Chertow, Glenn M.
    AMERICAN JOURNAL OF KIDNEY DISEASES, 2015, 65 (04) : A25 - A25
  • [42] UV disinfection in a model distribution system: biofilm growth and microbial community
    Pozos, N
    Scow, K
    Wuertz, S
    Darby, J
    WATER RESEARCH, 2004, 38 (13) : 3083 - 3091
  • [43] Impact of UV and secondary disinfection on microbial control in a model distribution system
    Dykstra, Trevor S.
    O'Leary, Kevin C.
    Chauret, Christian
    Andrews, Robert C.
    Gagnon, Graham A.
    JOURNAL OF ENVIRONMENTAL ENGINEERING AND SCIENCE, 2007, 6 (02) : 147 - 155
  • [44] Thinking Outside the Treatment Plant: UV for Water Distribution System Disinfection
    Linden, Karl G.
    Hull, Natalie
    Speight, Vanessa
    ACCOUNTS OF CHEMICAL RESEARCH, 2019, 52 (05) : 1226 - 1233
  • [45] UV LED water disinfection: Validation and small system demonstration study
    Hull, Natalie M.
    Herold, William H.
    Linden, Karl G.
    AWWA WATER SCIENCE, 2019, 1 (04):
  • [46] UV Disinfection Robots: A Review
    Mehta, Ishaan
    Hsueh, Hao-Ya
    Taghipour, Sharareh
    Li, Wenbin
    Saeedi, Sajad
    ROBOTICS AND AUTONOMOUS SYSTEMS, 2023, 161
  • [47] Emerging trends in UV disinfection
    McClean, Jon
    Water and Wastes Digest, 2007, 47 (05):
  • [48] Storm water disinfection with UV
    Meyer, Kirsten (kirsten.meyer@xyleminc.com), 2016, Scranton Gillette Communications Inc. (55):
  • [49] Sewerage disinfection with UV rays
    Huber, S
    GESUNDHEITSWESEN, 2006, 68 (03) : 201 - 202
  • [50] UV GREEN LIGHT DISINFECTION
    MORGAN, R
    DAIRY INDUSTRIES INTERNATIONAL, 1989, 54 (11) : 33 - &