Effect of UV system modifications on disinfection performance

被引:25
|
作者
Chiu, KP
Lyn, DA
Savoye, P
Blatchley, ER
机构
[1] Trojan Technol Inc, London, ON N5V 4T7, Canada
[2] Purdue Univ, Sch Civil Engn, W Lafayette, IN 47907 USA
[3] Ctr Int Rech Eau & Environm, Le Pecq, France
来源
关键词
D O I
10.1061/(ASCE)0733-9372(1999)125:5(459)
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Numerical simulations have been performed to gain a better understanding of ultraviolet (UV) disinfection process performance. Similar simulations in previous studies revealed critical paths through which particles moved and experienced low UV doses. In vertical UV systems, these paths generally are found near the channel walls with characteristics of high velocity and low turbulence intensity. Moreover, these paths generally coincide with low UV intensity zones and appear to represent the primary limitation of process performance. Reactor modifications have been designed to eliminate or modify these trajectories, thereby improving process performance. In a pilot-scale open-channel system with a vertical lamp orientation, two geometric modifications with "wave" and "baffle" shapes have been developed and examined. The results of these pilot tests confirmed the improvement of process performance when compared with an unmodified UV system. As in the case of the unmodified UV systems, a numerical model that combines kinetic information from a well-mixed batch reactor with a dose-distribution function was used to predict process performance of the UV system with the wave-shaped modification. A dose-distribution function that incorporates the effects of spatial nonuniformities in both hydrodynamics (through a random-walk model) and UV intensity (through a point-source-summation model) was developed. The dose-response function for microorganisms was obtained from completely mixed batch reactor experiments with a collimated beam. Predictions of disinfection efficacy confirmed the ability of the modified systems to improve microbial inactivation.
引用
收藏
页码:459 / 469
页数:11
相关论文
共 50 条
  • [1] Effect of UV system modifications on disinfection performance
    Chiu, Kuang-Ping
    Lyn, Dennis A.
    Savoye, Philippe
    Blatchley III, Ernest R.
    Journal of Environmental Engineering, 1999, 125 (05): : 459 - 469
  • [2] Effect of low turbidity and algae on UV disinfection performance
    Passantino, L
    JOURNAL AMERICAN WATER WORKS ASSOCIATION, 2004, 96 (06): : 128 - 137
  • [3] Effect of low turbidity and algae on UV disinfection performance
    Passantino, Laurel
    Malley Jr., James
    Knudson, Mark
    Ward, Robert
    Kim, Jae
    Journal / American Water Works Association, 2004, 96 (06): : 128 - 137
  • [4] Effect of low turbidity and algae on UV disinfection performance - Response
    Schaffner, R
    JOURNAL AMERICAN WATER WORKS ASSOCIATION, 2004, 96 (06): : 138 - 139
  • [5] The effect of a commercial UV disinfection system on the bacterial load of shell eggs
    De Reu, K
    Grijspeerdt, K
    Herman, L
    Heyndrickx, M
    Uyttendaele, M
    Debevere, J
    Putirulan, FF
    Bolder, NM
    LETTERS IN APPLIED MICROBIOLOGY, 2006, 42 (02) : 144 - 148
  • [6] UV disinfection system for cabin air
    Lim, Sojung
    Blatchley, Ernest R., III
    ADVANCES IN SPACE RESEARCH, 2009, 44 (08) : 942 - 948
  • [7] Troubleshooting your UV disinfection system
    Wright, Harold
    Heath, Mark
    Paranjape, Sudhan
    Cushing, Bob
    Leetch, Bob
    Parks, Robbie
    Garraway, Prentiss
    Cordova, Ed
    86th Annual Water Environment Federation Technical Exhibition and Conference, WEFTEC 2013, 2013, 9 : 5893 - 5909
  • [9] UV disinfection system downtime: Effects and mitigation
    Hubel, Richard E.
    JOURNAL AMERICAN WATER WORKS ASSOCIATION, 2007, 99 (04): : 140 - 147
  • [10] UV disinfection system downtime: Effects and mitigation
    Hubel, Richard E.
    1600, American Water Works Association (99):