Investigation on Dynamic Diffusion Behavior of Furfural in Oil-Pressboard Insulation under Partial Oil Replacement Condition

被引:0
|
作者
Liu, Jiefeng [1 ]
Geng, Chuhan [1 ]
Fan, Xianhao [1 ]
Zhang, Yiyi [1 ]
Zhang, Heng [1 ]
机构
[1] Guangxi Univ, Sch Elect Engn, Nanning, Guangxi, Peoples R China
基金
中国国家自然科学基金;
关键词
Analytical models; Correlation; Oils; Diffusion processes; Oil insulation; Aging; Chemicals; transformer; furfural; partial oil replacement; dynamic diffusion; POWER TRANSFORMERS; PAPER INSULATION; ASSET-MANAGEMENT; AGING ASSESSMENT; DEGRADATION;
D O I
10.1109/TDEI.2021.009476
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Furfural, as a typical chemical indicator, is used to evaluate the aging state of the cellulose insulation in the transformer. However, partial oil replacement will lead to the loss of furfural in oil and disturb the equilibrium distribution of furfural between oil and cellulose insulation, which could affect the evaluation results of the aging state of the cellulose insulation. Unfortunately, the influence of partial oil replacement has not been focused on. Given this issue, this work studies the influence of partial oil replacement on dynamic diffusion behavior of furfural in oil-pressboard insulation. First, the dynamic diffusion behavior of furfural between insulating pressboard and oil after partial oil replacement is discussed, and the theoretical diffusion model of furfural is established. Second, based on the mass gain curve of furfural in oil, the diffusion coefficients under different oil replacement ratios are obtained. Finally, a formula for calculating the diffusion equilibrium time is proposed. This paper attempts to report a method for analyzing the impact of the oil replacement ratio on the dynamic diffusion of furfural. These findings are expected to improve the accuracy of the aging assessment results by using furfural analysis.
引用
收藏
页码:1044 / 1052
页数:9
相关论文
共 50 条
  • [11] Influence of Fiber Impurities on DC Partial Discharge Process in Oil-pressboard Insulation
    Li, Yuan
    Zhang, Qiaogen
    Gao, Meng
    Ni, Heli
    Zhao, Yi
    Liu, Guangqi
    Wang, Ke
    [J]. 2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [12] PD Detection and Analysis of Oil-pressboard Insulation under Pulsed DC Voltage
    Li, Junhao
    Zhang, Liang
    Han, Xutao
    Yao, Xiu
    Li, Yanming
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) : 324 - 330
  • [13] Effect of Partial Oil Change on Furfural Partitioning in Oil-Paper-Pressboard Insulation System
    Zhang, Heng
    Liu, Jiefeng
    Geng, Chuhan
    Fan, Xianhao
    Zhang, Yiyi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (05) : 1612 - 1619
  • [14] PD Characteristics of Oil-pressboard Insulation under AC and DC Mixed Voltage
    Li, Junhao
    Han, Xutao
    Liu, Zehui
    Yao, Xiu
    Li, Yanming
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (01) : 444 - 450
  • [15] Influence of Nanoparticles on the Surface Discharge Marks in Oil-pressboard Insulation
    Chen Yilong
    Li Chengrong
    Du Yuefan
    Qi Bo
    Lv Yuzhen
    Li Xiaoxin
    Zhou You
    Tu Youping
    [J]. 2012 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2012, : 517 - 520
  • [16] Partial discharge characteristics and defect type identification of typical defects in oil-pressboard insulation
    Chi, Ming-He
    Xia, Ruo-Chun
    Luo, Qing-Lin
    Zhang, Chao-Hai
    Cao, Jin-Ming
    Guan, Yi
    Chen, Qing-Guo
    [J]. Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2022, 26 (02): : 121 - 130
  • [17] Effect of Voltage Waveform Steepness on Partial Discharge and Charge Distribution of Oil-Pressboard Insulation
    Zhu, Ran
    He, Dongxin
    Li, Shuqi
    Wang, Xuliang
    Gu, Yuanli
    Zhai, Yuhui
    Ma, Longfei
    Wang, Liangkai
    Liu, Hongshun
    Li, Qingquan
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (03) : 1224 - 1232
  • [18] Exploration on breakdown mechanism of oil-pressboard insulation under polarity reversal voltage
    Wang, Yonghong
    Gao, Ziwei
    Zhu, Xuecheng
    Nie, Hongyan
    Chi, Minghe
    Chen, Qingguo
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2015, 35 (21): : 5656 - 5666
  • [19] AC Flashover Characteristic at the Triple Junction of the Oil-Pressboard Insulation
    Wen, Hao
    Cheng, Lin
    Jiang, Yi
    Zhu, Taiyun
    Chen, Zhong
    Hao, Jian
    [J]. IEEE ACCESS, 2020, 8 : 202660 - 202668
  • [20] Study on partial discharge and charge accumulation characteristics of oil-pressboard insulation under DC superimposed harmonic voltage
    Li, Shuqi
    Wang, Qiang
    He, Dongxin
    Wang, Liangkai
    Li, Qingquan
    Si, Wen
    [J]. HIGH VOLTAGE, 2023, 8 (06) : 1215 - 1224