Control of Legionella contamination in a hospital water distribution system by monochloramine

被引:31
|
作者
Marchesi, Isabella [1 ]
Cencetti, Stefano [2 ]
Marchegiano, Patrizia [2 ]
Frezza, Giuseppina [1 ]
Borella, Paola [1 ]
Bargellini, Annalisa [1 ]
机构
[1] Univ Modena & Reggio Emilia, Dept Publ Hlth Sci, I-41125 Modena, Italy
[2] Univ Hosp Policlin Modena, Modena, Italy
关键词
Legionella; Pseudomonas; Monochloramine; Chlorine dioxide; Hospital; Hot water distribution system; NOSOCOMIAL LEGIONNAIRES-DISEASE; ACQUIRED LEGIONELLOSIS; RISK; COLONIZATION;
D O I
10.1016/j.ajic.2011.03.008
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
Background: We report the results of 1-year application of monochloramine to control Legionella pneumophila contamination in a hospital hot water distribution system. Methods: In the main building of the hospital, a device continuously distributing monochloramine was installed. Legionella pneumophila and Pseudomonas spp contamination was followed in comparison with 2 other water networks in the same building using chlorine dioxide. Results: Monochloramine significantly reduced the number of contaminated sites compared with baseline (from 97.0% to 13.3%, respectively), chlorine dioxide device I ( from 100% to 56.7%, respectively), and device II (from 100% to 60.8%, respectively). No positive sample exceeded 104 colony-forming units/L versus 59.4% at baseline. Conclusion: Monochloramine could represent a good alternative to chlorine dioxide in controlling legionellae contamination in public and private buildings. Copyright (C) 2012 by the Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved.
引用
收藏
页码:279 / 281
页数:3
相关论文
共 50 条
  • [41] Contamination of the cold water distribution system of health care facilities by Legionella pneumophila: Do we know the true dimension?
    Arvand, M.
    Jungkind, K.
    Hack, A.
    [J]. EUROSURVEILLANCE, 2011, 16 (16) : 9 - 14
  • [42] Legionella control in the water system of antiquated hospital buildings by shock and continuous hyperchlorination: 5 years experience
    Orsi, Giovanni Battista
    Vitali, Matteo
    Marinelli, Lucia
    Ciorba, Veronica
    Tufi, Daniela
    Del Cimmuto, Angela
    Ursillo, Paolo
    Fabiani, Massimo
    De Santis, Susi
    Protano, Carmela
    Marzuillo, Carolina
    De Giusti, Maria
    [J]. BMC INFECTIOUS DISEASES, 2014, 14
  • [43] A 17-month evaluation of a chlorine dioxide water treatment system to control Legionella species in a hospital water supply
    Srinivasan, A
    Bova, G
    Ross, T
    Mackie, K
    Paquette, N
    Merz, W
    Perl, TM
    [J]. INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2003, 24 (08): : 575 - 579
  • [44] Legionella control in the water system of antiquated hospital buildings by shock and continuous hyperchlorination: 5 years experience
    Giovanni Battista Orsi
    Matteo Vitali
    Lucia Marinelli
    Veronica Ciorba
    Daniela Tufi
    Angela Del Cimmuto
    Paolo Ursillo
    Massimo Fabiani
    Susi De Santis
    Carmela Protano
    Carolina Marzuillo
    Maria De Giusti
    [J]. BMC Infectious Diseases, 14
  • [45] Legionella contamination in hot water of Italian hotels
    Borella, P
    Montagna, MT
    Stampi, S
    Stancanelli, G
    Romano Spica, V
    Triassi, M
    Marchesi, I
    Bargellini, A
    Tatò, D
    Napoli, C
    Zanetti, F
    Leoni, E
    Moro, M
    Scaltriti, S
    D'Alcalà, GR
    Santarpia, R
    Boccia, S
    [J]. APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 2005, 71 (10) : 5805 - 5813
  • [46] LEGIONELLA-PNEUMOPHILA IN A METROPOLITAN WATER DISTRIBUTION-SYSTEM
    VOSS, L
    BUTTON, KS
    TUOVINEN, OH
    [J]. ENVIRONMENTAL TECHNOLOGY LETTERS, 1985, 6 (10): : 429 - 438
  • [47] Efficacy of copper-silver ionization in controlling Legionella in a hospital hot water distribution system:: A German experience
    Mathys, W
    Hohmann, CP
    Junge-Mathys, E
    [J]. LEGIONELLA, 2002, : 419 - 424
  • [48] Legionella in water distribution systems
    Lin, YE
    Vidic, RD
    Stout, JE
    Yu, VL
    [J]. JOURNAL AMERICAN WATER WORKS ASSOCIATION, 1998, 90 (09): : 112 - 121
  • [49] Monochloramine decay in model and distribution system waters
    Vikesland, PJ
    Ozekin, K
    Valentine, RL
    [J]. WATER RESEARCH, 2001, 35 (07) : 1766 - 1776
  • [50] Peracetic acid in the disinfection of a hospital water system contaminated with Legionella species
    Ditommaso, S
    Biasin, C
    Giacomuzzi, M
    Zotti, CM
    Cavanna, A
    Moiraghi, AR
    [J]. INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2005, 26 (05): : 490 - 493