Control of Legionella contamination in a hospital water distribution system by monochloramine

被引:31
|
作者
Marchesi, Isabella [1 ]
Cencetti, Stefano [2 ]
Marchegiano, Patrizia [2 ]
Frezza, Giuseppina [1 ]
Borella, Paola [1 ]
Bargellini, Annalisa [1 ]
机构
[1] Univ Modena & Reggio Emilia, Dept Publ Hlth Sci, I-41125 Modena, Italy
[2] Univ Hosp Policlin Modena, Modena, Italy
关键词
Legionella; Pseudomonas; Monochloramine; Chlorine dioxide; Hospital; Hot water distribution system; NOSOCOMIAL LEGIONNAIRES-DISEASE; ACQUIRED LEGIONELLOSIS; RISK; COLONIZATION;
D O I
10.1016/j.ajic.2011.03.008
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
Background: We report the results of 1-year application of monochloramine to control Legionella pneumophila contamination in a hospital hot water distribution system. Methods: In the main building of the hospital, a device continuously distributing monochloramine was installed. Legionella pneumophila and Pseudomonas spp contamination was followed in comparison with 2 other water networks in the same building using chlorine dioxide. Results: Monochloramine significantly reduced the number of contaminated sites compared with baseline (from 97.0% to 13.3%, respectively), chlorine dioxide device I ( from 100% to 56.7%, respectively), and device II (from 100% to 60.8%, respectively). No positive sample exceeded 104 colony-forming units/L versus 59.4% at baseline. Conclusion: Monochloramine could represent a good alternative to chlorine dioxide in controlling legionellae contamination in public and private buildings. Copyright (C) 2012 by the Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved.
引用
收藏
页码:279 / 281
页数:3
相关论文
共 50 条
  • [1] Control of Legionella in drinking water systems:: Impact of monochloramine
    Kool, JL
    [J]. LEGIONELLA, 2002, : 411 - 418
  • [2] Effect of Monochloramine Treatment on Colonization of a Hospital Water Distribution System by Legionella spp.: A 1 Year Experience Study
    Mancini, Benedetta
    Scurti, Maria
    Dormi, Ada
    Grottola, Antonella
    Zanotti, Andrea
    Cristino, Sandra
    [J]. ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2015, 49 (07) : 4551 - 4558
  • [3] Effect of monochloramine treatment on the microbial ecology of Legionella and associated bacterial populations in a hospital hot water system
    Baron, Julianne L.
    Harris, J. Kirk
    Holinger, Eric P.
    Duda, Scott
    Stevens, Mark J.
    Robertson, Charles E.
    Ross, Kimberly A.
    Pace, Norman R.
    Stout, Janet E.
    [J]. SYSTEMATIC AND APPLIED MICROBIOLOGY, 2015, 38 (03) : 198 - 205
  • [4] Monochloramine and chlorine dioxide for controlling Legionella pneumophila contamination: biocide levels and disinfection by-product formation in hospital water networks
    Marchesi, Isabella
    Ferranti, Greta
    Bargellini, Annalisa
    Marchegiano, Patrizia
    Predieri, Guerrino
    Stout, Janet E.
    Borella, Paola
    [J]. JOURNAL OF WATER AND HEALTH, 2013, 11 (04) : 738 - 747
  • [5] CONTROL OF LEGIONELLA PNEUMOPHILA IN A HOSPITAL HOT WATER-SYSTEM
    SCHULZEROBBECKE, R
    JUNG, KD
    PULLMANN, H
    HUNDGEBURTH, J
    [J]. ZENTRALBLATT FUR HYGIENE UND UMWELTMEDIZIN, 1990, 190 (1-2): : 84 - 100
  • [6] THE CONTAMINATION OF HOSPITAL WATER SUPPLY SYSTEMS BY LEGIONELLA PNEUMOPHILA
    Tartakovsky, I. S.
    Gruzdeva, O. A.
    Sharapchenko, S. O.
    Gabrielyan, N., I
    [J]. VESTNIK TRANSPLANTOLOGII I ISKUSSTVENNYH ORGANOV, 2021, 23 (01): : 125 - 130
  • [7] Geostatistics - a tool applied to the distribution of Legionella pneumophila in a hospital water system
    Lagana, Pasqualina
    Moscato, Umberto
    Poscia, Andrea
    La Milia, Daniele Ignazio
    Boccia, Stefania
    Avventuroso, Emanuela
    Delia, Santi
    [J]. ANNALS OF AGRICULTURAL AND ENVIRONMENTAL MEDICINE, 2015, 22 (04) : 655 - 660
  • [8] A comprehensive evaluation of monochloramine disinfection on water quality, Legionella and other important microorganisms in a hospital
    Lytle, Darren A.
    Pfaller, Stacy
    Muhlen, Christy
    Struewing, Ian
    Triantafyllidou, Simoni
    White, Colin
    Hayes, Sam
    King, Dawn
    Lu, Jingrang
    [J]. WATER RESEARCH, 2021, 189
  • [9] Control of Legionella pneumophila contamination in a respiratory hydrotherapy system with sulfurous spa water
    Leoni, E.
    Sacchetti, R.
    Zanetti, F.
    Legnani, P. P.
    [J]. INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2006, 27 (07): : 716 - 721
  • [10] Safety and efficacy of chlorine dioxide for Legionella control in a hospital water system
    Zhang, Zhe
    McCann, Carole
    Stout, Janet E.
    Piesczynski, Steve
    Hawks, Robert
    Vidic, Radisav
    Yu, Victor L.
    [J]. INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2007, 28 (08): : 1009 - 1012