Research on the Lightning Intruding Overvoltage and Protection Measures of 500 kV AC Fault Current Limiter

被引:5
|
作者
Chen, Changfu [1 ]
Han, Yongxia [1 ]
Liu, Junxiang [2 ]
Mo, Wenxiong [2 ]
Yuan, Zhao [3 ]
Huang, Jianning [1 ]
Su, Haibo [2 ]
Zhang, Xiancong [2 ]
Wu, Kaijian [3 ]
机构
[1] South China Univ Technol, Sch Elect Power, Guangzhou 510641, Guangdong, Peoples R China
[2] Guangzhou Power Supply Co Ltd, Test & Res Inst, Guangzhou 514010, Guangdong, Peoples R China
[3] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Hubei, Peoples R China
基金
国家重点研发计划;
关键词
fault current limiter; overvoltage; high coupled split reactor; shunt capacitor; lightning impulse withstand voltage; TOWER;
D O I
10.3390/en12203845
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As one of the key technologies to solve the problem of high short-circuit current, the fault current limiter (FCL) has become a research hotspot in China and abroad. The overvoltage and protection measures of the FCL are the key technologies for its application. Therefore, this paper studies the lightning intruding overvoltage and protection measures for a 500 kV FCL based on a high coupled split reactor (HCSR). Firstly, according to the main topology of the system and the 500 kV HCSR-FCL structure, the lightning intruding overvoltage simulation model of the 500 kV station, including the nearby transmission lines, is established on the PSCAD (Power Systems Computer Aided Design) program. Secondly, the lightning overvoltage of the equipment in the station and the components of the HCSR-FCL are simulated and analyzed when the transmission lines nearby are subjected to lightning shielding failure and back flashover. Meanwhile, the influence of the HCSR-FCL on the lightning overvoltage of the equipment in the station are compared and analyzed before and after the HCSR-FCL is installed. The simulation results show that the overvoltage of the equipment in the station and the components of the HCSR-FCL is more serious when the shielding failure occurs in the transmission lines nearby. The HCSR-FCL can reduce the lightning overvoltage of the equipment in the station, but the maximum inter-terminal and inter-arm lightning overvoltage of the HCSR can reach 1064 kV and 790 kV, respectively, under the current limiting state and the current sharing state. Finally, methods of increasing the arresters on the transmission lines side of the HCSR-FCL and shunt capacitor between each module of the HCSR-FCL are proposed to reduce the lightning overvoltage. The lightning impulse withstand voltage of each component of the HCSR is also proposed: The inter-terminal lightning impulse withstand voltage of HCSR is 170 kV. The inter-arm lightning impulse withstand voltage of HCSR is 200 kV. The terminal-to-ground lightning impulse withstand voltage of the HCSR-FCL is 1550 kV.
引用
收藏
页数:17
相关论文
共 50 条
  • [31] Design and Test of 500-kV Lightning Protection Insulator
    Jiang, Zhenglong
    Wu, Wei
    Wang, Bowen
    Xie, Pengkang
    Li, Hua
    Lin, Fuchang
    IEEE ACCESS, 2019, 7 : 135957 - 135963
  • [32] Analysis of influence of a novel inductive fault current limiter on the circuit breaker in 500-kV power system
    Tang, Qiang
    Jia, Shenli
    Zhang, Yanzhe
    Xiu, Shixin
    Mo, Wenxiong
    Wang, Yong
    Su, Haibo
    HIGH VOLTAGE, 2021, 6 (06): : 997 - 1008
  • [33] Application of Fault Current Limiter in 22.9 kV KEPCO grid
    Kim, Min Jee
    Park, Kyungwon
    Ahn, Kil-Young
    Kim, Young-Geun
    Lim, Dong-Kyun
    2015 3RD INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2015, : 557 - 560
  • [34] Research on overvoltage and fault of a UHV AC/DC hybrid system
    Wang, Yali
    Zou, Liang
    Chen, Yongshuai
    Fang, Shengwei
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2106 - 2111
  • [35] 10 kV AC test verification of the high temperature superconducting fault current limiter with bias magnetic field
    Dong, Yujun
    Zhu, Jiahui
    Wei, Defu
    Chen, Wei
    Du, Qingqing
    Zhang, Ke
    Chen, Panpan
    Lu, Kun
    Jiang, Hao
    Wang, Shuai
    Liu, Jiaxing
    Guo, Tie
    Ding, Kaizhong
    CRYOGENICS, 2020, 112
  • [37] Compound ferroresonance overvoltage and fault current limiter for power system protectionInspec keywordsOther keywords
    Heidary, Amir
    Radmanesh, Hamid
    Bakhshi, Ali
    Samandarpour, Sahand
    Rouzbehi, Kumars
    Shariati, Negin
    IET ENERGY SYSTEMS INTEGRATION, 2020, 2 (04) : 325 - 330
  • [38] LIGHTNING PROTECTION OF 500 kv AIR INSULATED SUBSTATIONS - REVISITED.
    Nowell, R.S.
    Priest Jr., K.W.
    Proceedings of the Technical Programme - INTERNEPCON: International Electronic Packaging and Production Conferences, 1979, : 569 - 576
  • [39] Interruption Characteristics of High-speed Switches in 500 kV Fault Current Limiter with High Coupled Split Reactance
    Zhang, Yanzhe
    Xiu, Shixin
    Tang, Qiang
    Jia, Shenli
    Chu, Bo
    Mo, Wenxiong
    Wang, Yong
    Su, Haibo
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2023, 9 (04): : 1577 - 1584
  • [40] Assessment of lightning current parameters suitable for wind turbine overvoltage protection analysis
    Sarajcev, Petar
    Goic, Ranko
    WIND ENERGY, 2012, 15 (04) : 627 - 644