Research on the Lightning Intruding Overvoltage and Protection Measures of 500 kV AC Fault Current Limiter

被引:5
|
作者
Chen, Changfu [1 ]
Han, Yongxia [1 ]
Liu, Junxiang [2 ]
Mo, Wenxiong [2 ]
Yuan, Zhao [3 ]
Huang, Jianning [1 ]
Su, Haibo [2 ]
Zhang, Xiancong [2 ]
Wu, Kaijian [3 ]
机构
[1] South China Univ Technol, Sch Elect Power, Guangzhou 510641, Guangdong, Peoples R China
[2] Guangzhou Power Supply Co Ltd, Test & Res Inst, Guangzhou 514010, Guangdong, Peoples R China
[3] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Hubei, Peoples R China
基金
国家重点研发计划;
关键词
fault current limiter; overvoltage; high coupled split reactor; shunt capacitor; lightning impulse withstand voltage; TOWER;
D O I
10.3390/en12203845
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As one of the key technologies to solve the problem of high short-circuit current, the fault current limiter (FCL) has become a research hotspot in China and abroad. The overvoltage and protection measures of the FCL are the key technologies for its application. Therefore, this paper studies the lightning intruding overvoltage and protection measures for a 500 kV FCL based on a high coupled split reactor (HCSR). Firstly, according to the main topology of the system and the 500 kV HCSR-FCL structure, the lightning intruding overvoltage simulation model of the 500 kV station, including the nearby transmission lines, is established on the PSCAD (Power Systems Computer Aided Design) program. Secondly, the lightning overvoltage of the equipment in the station and the components of the HCSR-FCL are simulated and analyzed when the transmission lines nearby are subjected to lightning shielding failure and back flashover. Meanwhile, the influence of the HCSR-FCL on the lightning overvoltage of the equipment in the station are compared and analyzed before and after the HCSR-FCL is installed. The simulation results show that the overvoltage of the equipment in the station and the components of the HCSR-FCL is more serious when the shielding failure occurs in the transmission lines nearby. The HCSR-FCL can reduce the lightning overvoltage of the equipment in the station, but the maximum inter-terminal and inter-arm lightning overvoltage of the HCSR can reach 1064 kV and 790 kV, respectively, under the current limiting state and the current sharing state. Finally, methods of increasing the arresters on the transmission lines side of the HCSR-FCL and shunt capacitor between each module of the HCSR-FCL are proposed to reduce the lightning overvoltage. The lightning impulse withstand voltage of each component of the HCSR is also proposed: The inter-terminal lightning impulse withstand voltage of HCSR is 170 kV. The inter-arm lightning impulse withstand voltage of HCSR is 200 kV. The terminal-to-ground lightning impulse withstand voltage of the HCSR-FCL is 1550 kV.
引用
收藏
页数:17
相关论文
共 50 条
  • [21] Lightning Protection and Current Lightning Research
    Baumann, Michael
    Franchetti, Harald
    ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2010, 127 (05): : A42 - A42
  • [22] Research on a fault current limiter with TCSC
    Jia, Guixi
    Li, Hongfeng
    He, Jiali
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2005, 20 (11): : 20 - 25
  • [23] Research on Lightning Over-voltage Protection for 500kV GIS Substation
    Wang, Zhuo
    Li, Lei
    Gan, Ling Xia
    Li, Ning
    Li, Hong Tao
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3501 - 3505
  • [24] Design, Verification, and Protection Setting of Superconducting Fault Current Limiter for a 10 kV Power Network
    Zhu, Jiahui
    Yang, Qifan
    Chen, PanPan
    Zhang, Hongjie
    Li, Chao
    Wang, Qingshan
    JOURNAL OF SUPERCONDUCTIVITY AND NOVEL MAGNETISM, 2023, 36 (02) : 455 - 465
  • [25] Design, Verification, and Protection Setting of Superconducting Fault Current Limiter for a 10 kV Power Network
    Jiahui Zhu
    Qifan Yang
    PanPan Chen
    Hongjie Zhang
    Chao Li
    Qingshan Wang
    Journal of Superconductivity and Novel Magnetism, 2023, 36 : 455 - 465
  • [26] Tank-type Fast Switching of 500 kV Fast-switching Fault Current Limiter
    Wang W.
    Zhao Y.
    Xu Y.
    Lü W.
    Yang B.
    Fang T.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (02): : 803 - 811
  • [27] Simulation of neutral point overvoltage and research on new protection measures for 220kV transformer
    Chen Xiujuan
    Xia Chao
    Wu Guoxing
    Zhang Fan
    Ji Huizheng
    Wang Jianmin
    Shi Weidong
    Chen Long
    Lu Tiantian
    Lei Ting
    Zhang Zhaohua
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 582 - 587
  • [28] Research on fast fault identification method of 10.5 kV/1.5 kA superconducting fault current limiter
    Zhang, Zhifeng
    Sun, Qiang
    Xiao, Liye
    Liu, Daqian
    Qiu, Ming
    Qiu, Qinquan
    Zhang, Guomin
    Dai, Shaotao
    Lin, Liangzhen
    CRYOGENICS, 2014, 63 : 199 - 203
  • [29] Response of a 25 kV AC railway traction system to lightning current transients and mitigation measures
    Tlhabanyane, M. L.
    Gomes, C.
    2021 SOUTHERN AFRICAN UNIVERSITIES POWER ENGINEERING CONFERENCE/ROBOTICS AND MECHATRONICS/PATTERN RECOGNITION ASSOCIATION OF SOUTH AFRICA (SAUPEC/ROBMECH/PRASA), 2021,
  • [30] Lightning Protection Measures Research on Coal Mine 6kV Distribution Lines
    Wang, Yumei
    Zhang, Hao
    Yang, Xu
    ENGINEERING SOLUTIONS FOR MANUFACTURING PROCESSES, PTS 1-3, 2013, 655-657 : 872 - 875